COMMUNICATIONS GUIDE
ADDR
GROUP
(HEX)
1B15
Negative kvarh pulse output interval
1B16
Running time pulse relay
1B17
Running time pulse interval
1B18
Reserved
1B19
Reserved
...
...
1B1F
Reserved
LOSS OF
1B20
Loss of Comms Function
COMMS
1B21
Loss of Comms Function Type
1B22
Loss of Comms Port
1B23
Assign Loss of Comms Alarm Relay
1B24
Assign Loss of Comms Trip Relay
1B25
Loss of Comms Delay
1B26
Loss of Comms Alarm Event
1B27
Reserved
,,,
,,,
1B3F
Reserved
ANALOG
1B40
Analog output 1 selection
OUTPUTS
1B41
Analog output 2 selection
1B42
Analog output 3 selection
1B43
Analog output 4 selection
1B44
Phase A current minimum
1B46
Phase A current maximum
1B48
Phase B current minimum
1B4A
Phase B current maximum
1B4C
Phase C current minimum
1B4E
Phase C current maximum
1B50
Average phase current minimum
1B52
Average phase current maximum
1B54
AB line voltage minimum
1B55
AB line voltage maximum
1B56
BC line voltage minimum
1B57
BC line voltage maximum
1B58
CA line voltage minimum
1B59
CA line voltage maximum
1B5A
Average line voltage minimum
1B5B
Average line voltage maximum
1B5C
Phase AN voltage minimum
1B5D
Phase AN voltage maximum
1B5E
Phase BN voltage minimum
469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
Table 7: 469 MEMORY MAP (Sheet 45 of 90)
DESCRIPTION
STEP
MIN.
MAX.
VALUE
1
50000
1
0
3
1
1
50000
1
0
2
1
0
1
1
0
3
1
0
7
1
0
3
1
1
30
1
0
1
1
0
46
1
0
46
1
0
46
1
0
46
1
0
100000
1
0
100000
1
0
100000
1
0
100000
1
0
100000
1
0
100000
1
0
100000
1
0
100000
1
50
20000
1
50
20000
1
50
20000
1
50
20000
1
50
20000
1
50
20000
1
50
20000
1
50
20000
1
50
20000
1
50
20000
1
50
20000
1
MODBUS MEMORY MAP
FORMAT
UNITS
DEFAULT
CODE
kvarh
F1
1
--
F144
0
s
F1
0
--
F115
0 (Off)
--
F165
0 (Alarm)
0
--
F166
(COMP_R
S485)
--
F113
0 (Alarm)
--
F111
0 (Trip)
s
F1
1
--
F103
0 (NO)
--
F127
0
--
F127
0
--
F127
0
--
F127
0
A
F9
0
A
F9
100
A
F9
0
A
F9
100
A
F9
0
A
F9
100
A
F9
0
A
F9
100
V
F1
3200
V
F1
4500
V
F1
3200
V
F1
4500
V
F1
3200
V
F1
4500
V
F1
3200
V
F1
4500
V
F1
1900
V
F1
2500
V
F1
1900
63

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents