GE 469 Communications Manual page 52

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

MODBUS MEMORY MAP
ADDR
GROUP
(HEX)
15E4
Time to trip at 8.00 x FLA
15E6
Time to trip at 10.0 x FLA
15E8
Time to trip at 15.0 x FLA
15EA
Time to trip at 20.0 x FLA
15EC
Reserved
15ED
Reserved
...
...
15FF
Reserved
1600
Minimum allowable line voltage
1601
Stall current at minimum Vline
1602
Safe stall time at minimum Vline
1603
Acceleration intersect at minimum Vline
1604
Stall current at 100% Vline
1605
Safe stall time at 100% Vline
1606
Acceleration intersect at 100% Vline
1607
Reserved
1608
Reserved
...
...
163F
Reserved
SHORT
1640
Short circuit trip
CIRCUIT TRIP
1641
Overreach filter
1642
Short circuit trip relays
1643
Short circuit trip pickup
1644
Intentional short circuit trip delay
1645
Short circuit trip backup
1646
Short circuit backup relays
1647
Short circuit trip backup delay
1648
Reserved
1649
Reserved
---
---
164F
Reserved
OVERLOAD
1650
Overload alarm
ALARM
1651
Overload alarm relays
1652
Overload alarm events
1653
Overload alarm delay
1654
Reserved
1655
Reserved
...
...
165F
Reserved
MECHANICAL
1660
Mechanical jam trip
JAM
1661
Mechanical jam trip relays
48
Table 7: 469 MEMORY MAP (Sheet 30 of 90)
DESCRIPTION
STEP
MIN.
MAX.
VALUE
5
999999
1
5
999999
1
5
999999
1
5
999999
1
70
95
1
200
1500
1
5
9999
1
200
1500
1
200
1500
1
5
9999
1
200
1500
1
0
2
1
0
1
1
0
6
1
20
200
1
0
1000
10
0
1
1
0
2
1
10
2000
10
0
2
1
0
6
1
0
1
1
1
600
1
0
2
1
0
3
1
469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
COMMUNICATIONS GUIDE
FORMAT
UNITS
DEFAULT
CODE
s
F10
56
s
F10
56
s
F10
56
s
F10
56
%Rated
F1
80
× FLA
F3
480
s
F2
200
× FLA
F3
380
× FLA
F3
600
s
F2
100
× FLA
F3
500
--
F115
0
--
F103
0
--
F118
0
× CT
F2
100
ms
F1
0
--
F103
0
--
F119
0
ms
F1
200
--
F115
0
--
F113
0
--
F103
0
s
F2
0
--
F115
0
--
F111
0