COMMUNICATIONS GUIDE

Read Device Status

469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
Master Transmission
Slave Address
Function Code
Data Starting Address
Data
CRC (low, high)
Slave Response
Slave Address
Function Code
Data Starting Address
Data
CRC (low, high)
Modbus Implementation: Read Exception Status
469 Implementation: Read Device Status
This is a function used to quickly read the status of a selected device. A short message
length allows for rapid reading of status. The status byte returned will have individual bits
set to 1 or 0 depending on the status of the slave device.
469 General Status Byte:
Bit
Description
B0
1 TRIP relay operated = 1
B1
2 AUXILIARY relay operated = 1
B2
3 AUXILIARY relay operated = 1
B3
4 ALARM relay operated = 1
If status is neither stopped or running, the motor is starting or has been tripped.
Bytes
Example
1
0B
message for slave 11
1
06
store single setpoint
2
11 80
data starting at 1180h
2
01 F4
data for address 1180h
2
8D A3
computed CRC error code
Bytes
Example
1
0B
message from slave 11
1
06
store single setpoint value
2
11 80
data starting at 1180h
2
01 F4
data from address 1180h
2
8D A3
computed CRC error code
Bit
B4
5 BLOCK START relay operated = 1
B5
6 SERVICE relay operated = 1
B6
Stopped = 1
B7
Running = 1