GE 469 Communications Manual page 119

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

COMMUNICATIONS GUIDE
469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
Table 8: Data Formats (Sheet 7 of 15)
CODE
TYPE
Unsigned
ANALOG OUTPUT PARAMETER
16 bit integer
SELECTION
0
None
1
Phase A Current
2
Phase B Current
3
Phase C Current
4
Average Phase Current
5
AB Line Voltage
6
BC Line Voltage
7
CA Line Voltage
8
Average Line Voltage
9
Phase AN Voltage
10
Phase BN Voltage
11
Phase CN Voltage
12
Average Phase Voltage
13
Hottest Stator RTD
14
Hottest Bearing RTD
15
Ambient RTD
16
RTD #1
17
RTD #2
18
RTD #3
19
RTD #4
20
RTD #5
21
RTD #6
22
RTD #7
F127
23
RTD #8
24
RTD #9
25
RTD #10
26
RTD #11
27
RTD #12
28
Power Factor
29
Reactive Power
30
Real Power (kW)
31
Apparent Power
32
Thermal Capacity Used
33
Relay Lockout Time
34
Current Demand
35
kvar Demand
36
kW Demand
37
kVA Demand
38
Motor Load
39
Analog Input 1
40
Analog Input 2
41
Analog Input 3
42
Analog Input 4
43
Tachometer
44
MWhrs
45
Analog In Diff 1-2
46
Analog In Diff 3-4
MODBUS MEMORY MAP
DEFINITION
115