Set-Points; Program Soak Time - Fluke 7341 User Manual

Calibration bath
Hide thumbs Also See for 7341:
Table of Contents

Advertisement

set-points are independent from the programmable set-points described in Sec-
tion 9.3.1, Programmable Set-points.
Pn=8
Use the "UP" or "DOWN" buttons to change the number from 2 to 8.
Pn=3
Press "SET" to continue. Press "EXIT" to ignore any changes and to continue.
S
9.6.2

Set-points

The next parameters are the program set-points.
1 50.0
Use the "UP" or "DOWN" buttons to select any of the set-points.
3 30.0
Press "SET" to be able to change the set-point.
C 30.00
Use "UP" and "DOWN" to change the set-point value.
C 40.00
Press "SET" to save the new set-point value.
The other set-points can also be set in the same manner. Once the set-points are
programmed as desired press "EXIT" to continue.
E
9.6.3

Program Soak Time

The next parameter in the program menu is the soak time. This is the time, in
minutes, that each program set-point is maintained after settling before pro-
ceeding to the next set-point. The duration is counted from the time the temper-
ature reaches the set-point.
Pt=15
Use the "UP" or "DOWN" buttons to change the time.
Number of program set-points
New number of program set-points
Save new setting
First set-point
Third set-point
Set-point value
New set-point value
Continue to next menu function
Soak time in minutes
9 Controller Operation
Ramp and Soak Program
43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents