11 FSL100-TLX Test Lamp Hazardous Areas

The FSL100-TLX (test lamp) is an Intrinsically Safe (IS), battery operated, hand-held IR and UV radiation source that is
specifically designed to test Honeywell FSL100 series flame detectors in both safe and hazardous areas. The detection range is
approximately 4 meters (13 ft).
-

11.1 Safety Instructions

1.
Suitable for use in safe areas and IECEx zone 1, but only when properly assembled and in serviceable condition.
2.
This unit is intrinsically safe only while all covers and components are in place. Do not assemble, dissemble, remove covers
or replace batteries other than in a known safe area.
3.
The test lamp is only approved for testing Honeywell FSL100 flame detectors.
4.
Do not use the test lamp in wet conditions.
5.
The lamp does not contain any user replaceable parts other than the batteries. In the event of faults contact Honeywell
Analytics Technical Support for help.
6.
It is advisable to remove the batteries if storing the test lamp for any period of time. Battery leakage could damage the
equipment.
7.
Keep the test lamp and batteries away from children. Dispose of items in accordance with the WEEE directive.
8.
Do not mistreat or incinerate. The batteries could explode if exposed to intense heat.
According to local laws and regulations batteries should be disposed of separately from household waste. Take
MAN0987_Iss 2_09/16
ACCESSORIES
Figure 20.
Caution – WEEE Directive
them to a collection point designated by local authorities when they are no longer needed.
FSL100-TLX Test Lamp
36