Download Print this page

Perform A Walk Test; Troubleshooting - Honeywell 5800-OD Installation Instructions Manual

Wireless outdoor motion sensor

Advertisement

5800-OD Wireless Outdoor Motion Sensor – Installation Instructions
SET THE SENSITIVITY
1.
Set the Sensitivity Select Switch to the desired
sensitivity.
Notes:
When greater sensitivity is desired, select "H".
When conditions are poor select "L".
6

Perform a Walk Test

NOTE: With the Walk Test switch set to ON the LED will light when the detector is tripped, and the alarm is generated instantly.
1.
4.
Set the walk test
switch (DIP switch
1) to ON. Replace
the cover.
2.
5.
Perform a walk test
through the
detection area, and
verify satisfactory
results.
6.
3.
Allow the detection
area to remain
static and check for
false or unwanted
detections.
WALK TEST
7
Program the Control Panel
Prior to use in the system, you must "enroll" the transmitter's serial number in the control panel. Refer to the control panel's instructions for
further details. During programming, the transmitter shall be treated as RF supervised . (Mandatory for UL installations.)

TROUBLESHOOTING

SYMPTOM
No detection, when walking
through the detection area.
No detection occasionally, or poor
detection.
Low battery fault indicated on
system keypad display.
SET THE DIP SWITCHES
1.
Sensitivity
Select Switch
(L,M,H)
Notes:
If necessary, adjust
the detection area
If normal car or people
(see Perform Settings
traffic pass close to the
& Adjustments).
detection area, adjust the
detection area 1.5 to 2.0m
Repeat the walk test
(5 to 7ft) shorter to reduce
through the detection
false detections. This also
area, and verify
allows for changes due to
satisfactory results.
environmental thermal
Set the walk test
conditions.
switch to OFF, and
If the detection length is
secure the Cover with
adjusted to position "A"
the Captive Lock
[12m (40ft)], the detection
Screw.
area may increase when
there is a big temperature
difference between the
moving object and the
background.
This sensor has a multi-
level detection pattern
(from side view). A heat
source beyond the
detection area may cause
the detector to issue a
false alarm by reflecting
off the ground. Examples
include puddles, wet
surfaces, very smooth
asphalt or concrete
surfaces.
If this causes a problem,
adjust the detection
length to position "B".
Then perform a walk test
to verify satisfactory
results.
CAUSE
Batteries are incorrectly installed or
dead.
Wiring is faulty or loose.
Water in unit.
Transmitter or PIR sensor is faulty.
Sensitivity is set too low.
Detection area is not set correctly.
Batteries are very low or dead.
Set switch 2 for the desired
Battery Saving Timer
period.
Note: The alarm output
activations are limited by
the timer selection (5 or
120 seconds). Even if there
are continuous alarm
events, the alarm output
operates only once in the
selected timer period. This
can be 5 or 120 seconds.
120s – Default Setting
5s – Used when frequent
alarm transmission is re-
quired. Battery life will be
shortened when using this
setting.
REMEDY
Check for correct battery installation, or replace dead
batteries.
Check all connectors and wiring.
Check for cracks in the housing that would allow water
infiltration. Replace unit.
Replace unit.
Try a higher sensitivity setting.
Perform a Settings & Adjustments procedure.
Replace batteries.
4
2.
Set switch 3 for the desired Pulse Count
(selectable for 2 or 4).
Pulse Count of 2 = detection can be made with
as little as two steps.
Pulse Count of 4 = detection can be made with
as little as four steps.
3.
Set switch 1 to enable the Walk Test, see the
instructions below.
ON 1. Walk Test
OFF
5s
2. Battery Saving Timer
120s
2
3. Pulse Count
4
If this causes a problem, adjust the detection length
to position "B". Then walk test to verify satisfactory
results.
Approx.8m (27ft)
position B
Approx.12m (40ft)

Advertisement

loading