Environmental; Performance; Hazardous Area Classifications; Performance Certifications - Honeywell FS20X Series User Manual

Fire and flame detectors
Hide thumbs Also See for FS20X Series:
Table of Contents

Advertisement

Environmental

Description
Operating Temperature,
Standard
Operating Humidity Range
Storage Temperature

Performance

Description
Field of View
Sensitivity
Speed of Response
Spectral Sensitivity
Wire Temperature Rating

Hazardous Area Classifications

(See
"Hazardous Location Detector Markings" on page
Class I, Division 1, Groups A, B, C & D
Class II, Division 1 Groups E, F & G
Class III Ex db IIC, Ex tb IIIC
T4: Ta = -40°C to +110°C
T5: Ta = -40°C to +75°C
T6: Ta = -40°C to +60°C

Performance Certifications

(See
"Hazardous Location Detector Markings" on page
Agency
Standard
LPCB
EN 54-10:2002 +A1:2005 1175a/01
CPR
EN 54-10:2002 +A1:2005 0832-CPR-F0515
FS20X Fire and Flame Detectors
-40° F to +185° F (-40° C to +85° C)
0 to 95% RH, 100% RH condensing for short periods of time
-67° F to +221° F (-55° C to +105° C)
cone of view is 90° horizontal and 80° vertical (35° above
the center line and 45° below it)
1 sq. ft. heptane fire at 200 feet (± 45° from axis)
typically 2 to 5 seconds
~0.185 to 0.26 microns and 0.4 microns to 3.5 microns
must be rated at least 10°C above the rated service temperature
(120°C for T4 applications, 85°C for T5 applications)
Description
Class I, Zone 1, AEx d/ Ex d IIC
T4: Ta = -40°C to +110°C
T5: Ta = -40°C to +75°C
T6: Ta = -40°C to +60°C
Certificate
Value
Value
42)
42)
Notes
Sensitivity settings: Very
High, High, Medium
EN 54-10 Class 1
39

Advertisement

Table of Contents
loading

Table of Contents