3
3.11.3
Figure 3.9 Converting the gas control SCE 65-500
36
Installation
12. If the flat sealing plate or burner pressure regulator has to be replaced:
-
Unscrew the connector efrom the gas control.
-
If required, disassemble the flat sealing plate f or burner pressure
regulator d.
-
If required, fit the flat sealing plate or burner pressure regulator from
the conversion kit.
-
Fit the connector e for the gas control.
13. Check the burner pressure and supply pressure (see paragraph 3.12).
14. Remove the sticker from the conversion kit, which shows the category of gas
that has just been set and stick it under the appliance's rating plate. This
clearly indicates that the appliance no longer operates on the gas for which
it was originally supplied.
15. Put the appliance into operation (see paragraph 7.2).

Convert to another category of gas SCE 65-500

Introduction
This paragraph describes the:
Converting from LP gas to natural
Converting from natural gas to LP
1
Converting from LP gas to natural gas
1. Complete steps 1 to 9 in paragraph
category SCE 80-115 to 65-400 incl.'
2. Disassemble the high-low regulator 2.
3. Fit the burner pressure regulator
conversion kit. Fasten the burner pressure regulator to the gas control with
the two small screws that are supplied 3.
gas.
gas.
2
3
IMD-0132
'3.11.2 Conversion to another gas
including the sealing packing from the
1