Operating Guide ECL Comfort 210 / 310, application A231 / A331
5.10 Alarm
The alarm function activates A1 (relay 4).
The alarm relay can activate a lamp, a horn, an input to an alarm
transmitting device etc.
The alarm relay is activated:
•
as long as the alarm reason is present (automatic reset)
or
•
even if the alarm reason disappears again (manual reset)
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
5.10.1 Temp. monitor.
MENU > Settings > Alarm
Upper difference
The alarm is activated if the actual flow / duct temperature increases more
than the set difference (acceptable temperature difference above the desired
flow / duct temperature). See also 'Delay' .
See Appendix "Parameter ID overview"
OFF:
The related alarm function is not active.
Value:
The alarm function is active if the actual temperature
gets above the acceptable difference.
88 | © Danfoss | 2017.11
Upper difference
1x147
=
X
Time
=
Y
Temperature
=
# 1 #
Upper difference
=
# 2 #
Desired flow temperature
VI.LG.P2.02
Need help?