Danfoss ECL Comfort 210 Operating Manual page 76

Application a231 / a331
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210 / 310, application A231 / A331
MENU > Settings > Pump control
Change, duration
The number of days between shift of circulation pumps. The shift takes place
at the time set in 'Change time' .
See Appendix "Parameter ID overview"
MENU > Settings > Pump control
Change time (changeover time)
The exact time of the day, where the shift must take place. The day is divided
into 24 hours. The factory setting here is 12 which means 12:00 (noon).
See Appendix "Parameter ID overview"
MENU > Settings > Pump control
Stab. time (stabilization time)
Setting of max. time to elapse between pump start command and feedback
from differential pressure switch.
If the differential pressure switch does not give feedback within the set time,
the alarm will be activated and the other pump will get a start command.
See Appendix "Parameter ID overview"
76 | © Danfoss | 2017.11
1x311
= Time
X
# 1 # = Pump P3
# 2 # = Pump P5
# 3 # = Change, duration (days)
1x312
= Time
X
# 1 # = Pump P3
# 2 # = Pump P5
# 3 # = Change time (clock time)
1x313
If the chosen stabilization time ('Stab. time') is too short, the active
pump will stop immediately after the stabilization time has elapsed.
VI.LG.P2.02