Operating Guide ECL Comfort 210 / 310, application A231 / A331
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Refill water
P exercise (pump exercise)
The time the pump is activated during exercise. Exercise takes place every
day (at 12:00).
See Appendix "Parameter ID overview"
OFF:
No pump exercise.
1 ... 200: Activation time during exercise.
MENU > Settings > Refill water
Pressure, des. (desired pressure)
Read out of the calculated desired pressure at the inlet / outlet.
Access to conversion (scale) settings: Push dial.
See Appendix "Parameter ID overview"
Set the relationship between outdoor temperature and desired
pressure.
MENU > Settings > Refill water
Pressure, diff. (switching difference)
Setting of the switching difference for measured static pressure (pressure
transmitter). The difference is symmetrical around the 'Pressure des. ' See
also 'Pressure des. '
See Appendix "Parameter ID overview"
VI.LG.P2.02
1x320
= Outdoor temperature
X
= Desired pressure (Pascal)
Y
1x322
The settings in 'Pressure, des.' and 'Pressure, diff.' have no influence
when a pressure switch is used.