CHAPTER 5: SETTINGS

5.7.9 Breaker failure (ANSI 50BF)

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  BREAKER FAILURE  BREAKER FAILURE 1(4)
 BREAKER FAILURE 1
F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-133: Negative-sequence directional OC1 logic
BF1 FUNCTION:
Disabled
BF1 MODE:
3-Pole
BF1 SOURCE:
SRC 1
BF1 USE AMP SUPV:
Yes
BF1 USE SEAL-IN:
Yes
BF1 3-POLE INITIATE:
Off
BF1 BLOCK:
Off
BF1 RETRIP PICKUP
DELAY: 0.033 s
BF1 PH AMP SUPV
PICKUP: 1.050 pu
BF1 N AMP SUPV
PICKUP: 1.050 pu
BF1 USE TIMER 1:
Yes
GROUPED ELEMENTS
Range: Disabled, Enabled
Range: 3-Pole, 1-Pole
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: Yes, No
Range: Yes, No
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.020 to 30.000 pu in steps of 0.001
Range: 0.020 to 30.000 pu in steps of 0.001
Range: Yes, No
5
5-253