CHAPTER 6: ACTUAL VALUES

6.5 Records

6.5.1 Fault reports

ACTUAL VALUES  RECORDS  FAULT REPORTS  FAULT REPORT 1(15)
NO FAULTS TO REPORT
or
 FAULT REPORT 1
The latest 15 fault reports can be stored. The most recent fault location calculation (when applicable) is displayed in this
menu, along with the date and time stamp of the event which triggered the calculation. See the
menu for assigning the source and trigger for fault calculations. See the
SETUP  FAULT REPORTS
menu for manual clearing of the fault reports and to the
RECORDS
menu for automated clearing of the fault reports.
Where VA, VB, VC are phase voltage phasors in secondary volts; IA, IB, IC are current phasors in secondary amps, I0 is the
zero sequence current phasors in secondary amps; and IG is the ground current from the parallel line scaled to the source
phase CT in secondary amps. Z0/Z1 is the zero sequence impedance to positive sequence impedance ratio, and Z0M/Z1 is
mutual zero sequence impedance to positive sequence impedance ratio.
VTs of the
FAULT REPORT 1 SOURCE
connected VT to display the loop impedance and fault resistance for single phase-to-ground faults.

6.5.2 Event records

6.5.2.1 Enhanced and standard front panels
ACTUAL VALUES  RECORDS  EVENT RECORDS
 EVENT RECORDS
F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
FAULT 1
LINE ID: SRC 1
FAULT 1
DATE:
2000/08/11
FAULT 1
TIME:
00:00:00.000000
FAULT 1
TYPE:
ABG
FAULT 1
LOCATION
00.0 km
FAULT 1
RECLOSE
SHOT: 0
must be connected in Wye or
EVENT: XXX
XXX
EVENT: 3
POWER ON
EVENT: 2
POWER OFF
EVENT: 1
EVENTS CLEARED
Range: SRC 1, SRC 2
Range: YYYY/MM/DD
Range: HH:MM:SS.ssssss
Range: not available if the source VTs are in the
"Delta" configuration
Range: not available if the source VTs are in the
"Delta" configuration
Range: where applicable
SETTINGS  PRODUCT SETUP  CLEAR RELAY RECORDS
must be set correctly for the Delta
VT SUBSTITUTION
Date and time stamps
EVENT 3
DATE: 2000/07/14
EVENT 3
TIME: 14:53:00.03405
RECORDS