Wattmetric Ground Fault - GE F60 Instruction Manual

Feeder protection system
Hide thumbs Also See for F60:
Table of Contents

Advertisement

GROUPED ELEMENTS
5

5.7.6 Wattmetric ground fault

5.7.6.1 Wattmetric zero-sequence directional (ANSI 32N, IEC PSDE)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  WATTMETRIC...  WATTMETRIC GROUND FAULT 1(2)
 WATTMETRIC
 GROUND FAULT 1
5-236
Figure 5-122: Neutral directional overcurrent logic
WATTMETRIC GND FLT 1
FUNCTION: Disabled
WATTMETRIC GND FLT 1
SOURCE: SRC 1
WATTMETRIC GND FLT 1
VOLT: Calculated VN
WATTMETRIC GND FLT 1
OV PKP: 0.20 pu
WATTMETRIC GND FLT 1
CURR: Calculated IN
WATTMETRIC GND FLT 1
OC PKP: 0.060 pu
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: Calculated VN, Measured VX
Range: 0.02 to 3.00 pu in steps of 0.01
Range: Calculated IN, Measured IG
Range: 0.002 to 30.000 pu in steps of 0.001
F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS

Advertisement

Table of Contents
loading

Table of Contents