CHAPTER 5: SETTINGS
Actions based on RTD overtemperature, such as trips or alarms, are done in conjunction with the FlexElements feature. In
FlexElements, the operate level is scaled to a base of 100°C. For example, a trip level of 150°C is achieved by setting the
operate level at 1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output
contact directly.
See the following table for reference temperature values for each RTD type.
Table 5-45: RTD temperature vs. resistance
Temperature
Resistance (in ohms)
°C
°F
100 Ω Pt
(DIN 43760)
–50
–58
80.31
–40
–40
84.27
–30
–22
88.22
–20
–4
92.16
–10
14
96.09
0
32
100.00
10
50
103.90
20
68
107.79
30
86
111.67
40
104
115.54
50
122
119.39
60
140
123.24
70
158
127.07
80
176
130.89
90
194
134.70
100
212
138.50
110
230
142.29
120
248
146.06
130
266
149.82
140
284
153.58
150
302
157.32
160
320
161.04
170
338
164.76
180
356
168.47
190
374
172.46
200
392
175.84
210
410
179.51
220
428
183.17
230
446
186.82
240
464
190.45
250
482
194.08

5.11.3 DCmA outputs

SETTINGS  TRANSDUCER I/O  DCMA OUTPUTS  DCMA OUTPUT H1(W8)
 DCMA OUTPUT H1
F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
120 Ω Ni
100 Ω Ni
86.17
71.81
92.76
77.30
99.41
82.84
106.15
88.45
113.00
94.17
120.00
100.00
127.17
105.97
134.52
112.10
142.06
118.38
149.79
124.82
157.74
131.45
165.90
138.25
174.25
145.20
182.84
152.37
191.64
159.70
200.64
167.20
209.85
174.87
219.29
182.75
228.96
190.80
238.85
199.04
248.95
207.45
259.30
216.08
269.91
224.92
280.77
233.97
291.96
243.30
303.46
252.88
315.31
262.76
327.54
272.94
340.14
283.45
353.14
294.28
366.53
305.44
DCMA OUTPUT H1
SOURCE: Off
DCMA OUTPUT H1
RANGE: –1 to 1 mA
TRANSDUCER INPUTS/OUTPUTS
10 Ω Cu
7.10
7.49
7.88
8.26
8.65
9.04
9.42
9.81
10.19
10.58
10.97
11.35
11.74
12.12
12.51
12.90
13.28
13.67
14.06
14.44
14.83
15.22
15.61
16.00
16.39
16.78
17.17
17.56
17.95
18.34
18.73
Range: Off, any analog actual value parameter