Negative Pressure; Draft; Chimney And Exhaust Connection - Quadra-Fire SANTAFEI-MBK Installation Manual

Hide thumbs Also See for SANTAFEI-MBK:
Table of Contents

Advertisement

Santa Fe Pellet Insert
C. Negative Pressure
Negative pressure results from the imbalance of air avail-
able for the appliance to operate properly. It can be strongest
in lower levels of the house.
Causes include:
• Exhaust fans (kitchen, bath, etc.)
• Range hoods
• Combustion air requirements for furnaces, water
appliances and other combustion appliances
• Clothes dryers
• Location of return-air vents to furnace or air conditioning
• Imbalances of the HVAC air handling system
• Upper level air leaks such as:
- Recessed lighting
- Attic hatch
- Duct leaks
To minimize the effects of negative air pressure:
• Install the outside air kit with the intake facing prevailing
winds during the heating season
• Ensure adequate outdoor air for all combustion appliances
and exhaust equipment
• Ensure furnace and air conditioning return vents are not
located in the immediate vicinity of the appliance
• Avoid installing the appliance near doors, walkways or
small isolated spaces
• Recessed lighting should be a "sealed can" design
• Attic hatches weather stripped or sealed
• Attic mounted duct work and air handler joints and seams
taped or sealed
WARNING
Risk of Asphyxiation!
Negative pressure can cause spillage of combustion
fumes and soot.
14
D. Draft
Draft is the pressure difference needed to vent an appli-
ance successfully. When an appliance is drafting suc-
cessfully, all combustion byproducts are exiting the home
through the chimney.
Install through the warm airspace enclosed by the build-
ing envelope. This helps to produce more draft, especially
during lighting and die-down of the fire.
Considerations for successful draft include:
• Preventing negative pressure
• Location of appliance and chimney
NOTICE: Hearth & Home Technologies assumes no
responsibility for the improper performance of the chimney
system caused by:
Inadequate draft due to environmental conditions
Down drafts
Tight sealing construction of the structure
Mechanical exhausting devices
E. Chimney and Exhaust Connection
1.
Chimney & Connector: Use 3 or 4 inch (76-102mm) diameter
type "L" or "PL" venting system. It can be vented vertically or
horizontally.
2. Mobile Home: Approved for all Listed pellet vent. If using the
3 inch (76mm) vertical Top Vent Adapter Kit or the 3 to 6 inch
(76-152mm) Top Vent Offset Adapter, use Listed double wall
flue connector. A Quadra-Fire Outside Air Kit must be used with
manufactured home installations.
3. Residential: The 3 inch (76mm) vertical Top Vent Adapter Kit and
the 3 to 6 inch (76-152mm) Top Vent Offset Adapter are tested
to use 24 gauge single wall flue connector or Listed double wall
flue connector to Class A Listed metal chimneys, or masonry
chimneys meeting International Residential Code standards for
solid fuel appliances.
4. INSTALL VENT AT CLEARANCES SPECIFIED BY THE
VENT MANUFACTURER.
5
. Secure exhaust venting system to the appliance with at least
3 screws. Also secure all connector pipe joints with at least 3
screws through each joint.
6. DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENT-
ING SYSTEM OF THIS Appliance.
7. DO NOT CONNECT THIS Appliance TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
NOTE: All pipe must be welded seam pipe whenever possible.
Seal pipe joints with high temperature silicone (500°F [260°C]
minimum rated only).
NOTE: If burning shelled field corn, you must use approved
venting specifically designed for corn. Follow the instructions
from the venting manufacturer.
7019-230G
June 5, 2017

Advertisement

Table of Contents
loading

Table of Contents