8.2.4 Fan speed has been out of control diagnosis and solution (E3)

Error Code
Malfunction conditions
Possible causes
Troubleshooting:
Shut off the power supply
and turn it on 2 minutes
later. Is it still displaying
the error code?
Yes
Shut off the power supply,
rotate the fan by hand.
Does it rotate properly?
Yes
Check the wires of fan
motor. Are all the
connections good?
Yes
Is the main PCB normal
through index 1 (next page)?
Yes
Replace the fan motor. Is the
error extinguished?
E3/F5
When indoor fan speed stays too low (300RPM) for certain time,
the unit will stop and the LED will display the failure.
Wiring error
Fan assembly faulty
Fan motor faulty
PCB faulty
No
No
No
No
40
The unit operates normally.
Find the cause and
repair. For example,
check whether the fan
is blocked or the
bearing is broken?
Correct the connections.
Replace the main PCB
No
35