TECHNICAL DATA

Compressor:
Power Source:
Amperage:
Run Load Amps:
Locked Rotor Amps:
Size:
*UL Certified Rates to ARI Standard 740-98
RecoverXL
Vapor lbs./min
Liquid lbs./min
Push-Pull lbs./min
Vacuum Level
RecoverXLT
Vapor lbs./min
Liquid lbs./min
Push-Pull lbs./min
Vacuum Level
Other Refrigerants - The RecoverXL/XLT is approved for use with the following refrigerants which
have not been certified for a particular recovery rate: R401B, R-402A, R-402B, R-404A, R-406A,
R-407A, R-407B, R-407C, R-407D, R-408A, R-409A, R-411A, R-411B, R-500 and R-502.
Suction Filter
The RecoverXL/XLT is equipped with a built-in
particulate strainer located behind the suction
port. Unscrew the suction port by using a 11/16
wrench to unscrew the hex head port to remove.
This prevents contaminants, copper shavings,
carbon, and other foreign objects from making
their way to the RecoverXL/XLT compressor and
causing permanent damage.
Like a filter drier, this strainer MUST be cleaned
or replaced often. Failure to do this can cause the
strainer to become too clogged for refrigerant to
flow freely. A sure sign that the straining device is
10
1/2 HP Reciprocating Oil-Less
115V AC 60 Hz 1 Phase
Full Load Amps:
Height:
Width:
Depth:
Weight:
R-12
R-134a
.31
1.68
13.12
15 inHg
15 inHg
R-12
R-134a
.37
1.98
12.81
15 inHg
15 inHg
9.3
11.0
30.0
R-22
.31
.31
1.68
1.68
13.12
13.12
15 inHg
R-22
.37
.37
1.98
1.98
12.81
12.81
15 inHg
clogged is the freezing of the suction port and the
filter cover.
Before replacing, check the condition of the
o-ring. Replace if necessary.
Note: Make sure to use a strainer in the
RecoverXL/XLT for every job! Filter strainers
and o-rings are available from your supplier.
Filter Strainer and O-Ring - Part #95457
230V AC 50 Hz 1 Phase
3.7
11.0
18.0
12.50"
12.50"
19.25"
29.90"
R-500
R-502
.31
.55
1.68
2.29
13.12
13.18
15 inHg
15 inHg
R-500
R-502
.37
.66
1.98
2.65
12.81
12.9
15 inHg
15 inHg
R-410A
.42
1.41
11.6
15 inHg
R-410A
.42
1.68
11.6
15 inHg