99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.TestEquipmentDepot.com YJ-LTE Oil-Less Universal ™ Refrigerant Recovery System Operation and Maintenance Manual (English and Spanish. French and German available at www.yellowjacket.com)
IMPORTANT NOTICE TO PURCHASER Check for damage immediately. Prior to Engineering will cooperate in assessing shipment, all YELLOW JACKET YJ-LTE damage if the recovery system is returned Refrigerant Recovery Systems are com- to the factory prepaid. pletely tested and inspected to assure com-...
liquid. Do not allow refrigerants to come in ment or create a hazard. contact with open flame. Refrigerant decom- 12) Use the YJ-LTE only with the proper position in flame can result in the formation refrigerants. (See specifications for a of hydrofluoric acid or phosgene gas.
5. Connect the recovery hose from system or 10. Open the utility valve and then slowly utility port of your manifold to the 1/4” open the high side first to recover as much liquid as possible, then open low side and SUCTION port of the YJ-LTE.
The push-pull process requires the following: will allow a faster liquid recovery. Proper hoses for all connections. Hoses Turn YJ-LTE on. If starting with an evacu- with low loss fittings or valves are recom- ated recovery cylinder allow as much liq- uid as possible to flow before starting mended.
Recovery Tips and Techniques 1) To assure the fastest and quickest 4) If recovering large amounts of recovery possible, use the shortest hoses refrigerant (20 lbs or more), the push- possible and use hoses with Schrader pull method is recommended. (Note: depressors only where necessary.