yellow jacket RecoverXLT2-AP Operation And Maintenance Manual

yellow jacket RecoverXLT2-AP Operation And Maintenance Manual

Oil-less universal refrigerant

Advertisement

Quick Links

RecoverXLT2-AP
Oil-Less Universal
Refrigerant Recovery System
Operation and Maintenance
Manual
(English)

Advertisement

Table of Contents
loading

Summary of Contents for yellow jacket RecoverXLT2-AP

  • Page 1 ™ RecoverXLT2-AP Oil-Less Universal Refrigerant Recovery System Operation and Maintenance Manual (English)
  • Page 2: Table Of Contents

    For best performance we recommend using 3/8” hoses. YELLOW JACKET hoses are made for 9) The RecoverXLT2-AP should not be used near almost every type of refrigerant. See your local open containers of gasoline or any other flamma- distributor for more information.
  • Page 3: Recoverxlt2-Ap Operation Guide

    AWG (1.276 mm RecoverXLT2-AP Operating Guide Direct Liquid/Vapor Recovery The RecoverXLT2-AP is used to pull liquid or vapor 3. Connect your manifold to the system being refrigerant out of the system and transfer it into a serviced. High Side to liquid port and Low Side recovery cylinder.
  • Page 4: Vapor Recovery

    11. Turn the RecoverXLT2-AP on. 6. Purge all hoses of non-condensables before recovering refrigerant into recovery cylinder. Note: The RecoverXLT2-AP will turn on and run for approx. six seconds before the compres- 7. Open the liquid valve on the recovery tank.
  • Page 5: System Purge Instructions

    OFF the duce the risk of cross contamination and prolong the equalize then to PURGE. Turn the system life of the RecoverXLT2-AP by purging after every switch ON. service. Note: The low side gauge should read an...
  • Page 6: Recovering R-410A High Pressure Gas

    PURGE position and follow procedures for purging the RecoverXLT2-AP. Note: See pages 3-4 for a detailed set of instructions on Vapor Recovery. 10) Turn the RecoverXLT2-AP off. Push-Pull Recovery Diagram Recovering R-410A High Pressure Gas IMPORTANT!!! Some equipment should not be Follow the operating procedures for your used with this refrigerant.
  • Page 7: Suction Filter

    Port of the RecoverXLT2-AP. how much refrigerant will be recovered. The first job of the day usually means a fresh, 6) Protect the RecoverXLT2-AP by keeping the empty tank and no cause for worry about over built-in suction filter IN THE MACHINE.
  • Page 8: Troubleshooting Guide

    Ambient Pressure Switch tripped Pressurize inlet port before power up. Unit has not ventilated the cabinet yet The RecoverXLT2-AP fan will run for approximately six seconds before the compressor starts up to prevent un- wanted mixtures of gas from building up inside the unit.
  • Page 9: Technical Data

    Technical Data 1/2 HP Reciprocating Oil-Less Compressor: Power Source: 230V AC 50/60 Hz 1 Phase Size: Height: 12.50” Width: 12.50” Depth: 19.25” Weight: 29.90” Calculated Recovery Ratings Kg./minute Kg./hour Vapor Push/Pull Liquid Vapor Push/Pull Liquid 0.17 4.16 3.10 R-22 .011 3.41 2.53 R-32...
  • Page 10: Important Notice To Purchaser

    The following exceptions will not be covered If at any time after the warranty period you under this warranty: Recovery products that have have problems with your YELLOW JACKET been altered, misused, or improperly maintained. recovery unit, call our technical service depart-...