Facility Requirements; Power Supply Specifications - Brocade Communications Systems VDX 6710 Hardware Reference Manual

Table of Contents

Advertisement

DRAFT: BROCADE CONFIDENTIAL
A

Facility requirements

Facility requirements
Table 7
TABLE 7
Type
Electrical
Thermal
Cabinet (when
rack-mounted)

Power supply specifications

The power supplies are universal and capable of functioning worldwide without voltage jumpers or
switches. They meet IEC 61000-4-5 surge voltage requirements and are autoranging in terms of
accommodating input voltages and line frequencies.
Table 8
TABLE 8
Specification
Maximum output
Maximum AC power consumption
System DC power consumption (excluding power supply
and fan FRUs)
Input system power (including power supply and fan
FRUs)
Input voltage
Input line frequency
Inrush current
Input line protection
40
provides the facilities requirements that must be met for the Brocade VDX 6710 switches.
Facility requirements
Requirements
Primary AC input 85-265 VAC nominal, 47-63 Hz; switch autosenses input voltage
Adequate supply circuit, line fusing, and wire size, as specified by the electrical rating
on the switch nameplate
Circuit protected by a circuit breaker and grounded in accordance with local electrical
codes
Refer to
Table 8 on page 40
A nominal airflow of 74.8 cubic meters/hour (44 cubic ft/min.) and maximum of
101.9 cubic meters/hour (60 cubic ft/min.) available in the immediate vicinity of the
switch
Ambient air temperature not exceeding 40
One rack unit (1U) in a 48.3 cm (19-inch) cabinet - VDX 6710
All equipment in cabinet grounded through a reliable branch circuit connection
Additional weight of switch not to exceed the cabinet's weight limits
Cabinet secured to ensure stability in case of unexpected movement
lists the power supply specifications for the Brocade VDX 6710 switches.
Power supply specifications
for complete power supply specifications.
°
°
C (104
F) while the switch is operating
Value
250 watts, 20.8 amps, 12 VDC - VDX 6710
156 W - VDX 6710
Idle: 182.4 W
Maximum: 306 W
Idle: 206 W
Maximum: 306 W
100-250 VAC, 50-60 Hz
47-63 Hz
Maximum of 50A
AC lines are fused
Brocade VDX 6710 Hardware Reference Manual