5.4.2
Connecting the AC/DC Unit to the Media Gateway Classic
When performing connections in the AC/DC unit, the outgoing battery, load,
symmetry, and alarm cables must have a service loop of minimum 0.3 m, see
Page 94 .
Table 32
25/BYB 501/1 Set of cables
Title/Function
HOLDER FOR STRAP
CABLE CLAMP (STRAP)
6/1531-ASP 113 01 Uen J2 2008-07-17
Fasten the screw (B) to secure the cable lug and press down the cover (I)
on the black minus pole (D).
Connect the black negative (-48V) DC supply cable (M) to the appropriate
negative DC distribution circuit breaker (Y) by inserting the stripped end in
the opening of the circuit breaker and tightening the screw.
Connect the cable lug (L) of the blue cable part of the TSR 903 0113/1
cable to the red plus pole (D) of the rightmost battery block, see Page
91 or Page 92.
Fasten the screw (B) to secure the cable lug and press down the cover
(I) on the red plus pole (D).
Connect the blue positive (+0V) DC supply cable (L) to the positive bus
bar/connector by inserting the stripped end to the hole of the screw
connector (X) so that the cable is behind the bus bar, and then tightening
the screw, see Page 91 or Page 92.
Connect the cable lug (M) of the grey cable part to the minus pole (D) of the
leftmost battery block, see Page 91 or Page 92.
Fasten the screw (B) to secure the cable lug and press down the cover (I)
on the black minus pole (D).
Connect the grey negative (-48V) DC supply cable (M) to the appropriate
negative DC distribution circuit breaker (Y) by inserting the stripped end in
the opening of the circuit breaker and tightening the screw.
Set of Cables
Product Number
SXA 123 0411/2
SET 103 02
Cabling
Quantity
40
40
93