Toshiba RAV-SM304MUT-E Service Manual page 98

Indoor unit digital inverter: compact 4-way cassette type; concealed duct type; ceiling type
Hide thumbs Also See for RAV-SM304MUT-E:
Table of Contents

Advertisement

No.
Part name
ƒ
Fan motor
Drain pan
Float switch
AMP Air Conditioning
Procedure
1. Remove the Multi blade fan.
2. Remove the hexagon head screw of fixing
fan motor holder.
3. Remove the fan motor holder
(2 positions).
1. Take down the main unit and then treat the
drain pan on the floor.
2. Remove the set screws (562 : 7, 802, 1102,
1402 : 9 positions) of fixing lower plate.
3. Remove the lower plate from main unit.
4. Remove the set screws (562 : Nothing, 802 :
2 positions, 1102, 1402 : 4 positions) of
fixing drain pan holder and main unit.
5. Remove the drain pan holder (562 : Nothing,
802 : 1 position, 1102, 1402 : 2 positions)
from main unit.
6. Remove the drain pan.
Pull it lower side.
1. Remove the drain pan.
2. Remove the set screw (1 position) of fixing
float switch holder.
3. Remove the plastics nut of foxing float
switch.
4. Remove the float switch.
Lower plate
Screws (Fixing drain pan holder)
Float switch
Float switch (View from reverse side)
Float switch holder
– 98 –
www.ampair.co.uk | sales@ampair.co.uk
Remarks
Fan motor holder
Fan motor
Screws
(Fixing fan motor holder)
Screws (Fixing lower plate)
Screws
(Fixing drain pan holder)
Drain pan holder
Drain pan
Float switch holder
Screw
(Fixing float switch holder)
Plastic nut
3 -2
3 -3
4 -2
4 -3
4 -4
4 -5
5 -2
5 -3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents