Toshiba RAV-SM304MUT-E Service Manual page 102

Indoor unit digital inverter: compact 4-way cassette type; concealed duct type; ceiling type
Hide thumbs Also See for RAV-SM304MUT-E:
Table of Contents

Advertisement

No.
Part name
Drain pan
Vertical grille
Louver motor,
Lover drive
member
AMP Air Conditioning
Procedure
1. Take down the main unit and then treat
the drain pan on the floor.
2. Remove the both side panels and suction
grilles.
3. (SM802, SM1102, SM1402CT-E only)
Remove the set screw (1 position) to
fixing and reinforcing bar.
(Slide the reinforcing bar toward arrow
side on the right figure.)
4. Remove the set screws (9 positions) of
fixing lower plate.
5. Remove the heat insulation on the drain
pan.
(SM562, SM802 : 1 position, SM1102,
SM1402 : 2 positions)
6. Remove the set screws
(SM562, SM802 : 1 position, SM1102,
SM1402 : 2 positions) of fixing drain pan
and main unit.
7. Remove the drain pan.
Pull it lower side.
1. Remove the drain pan.
2. Remove the set screws (2 positions) of
fixing vertical grille.
3. Remove the vertical grille.
1. Remove the side cover (right side only).
2. Remove the set screws (2 positions) and
louver motor.
3. Remove the set screws (2 positions) and
louver drive member.
Screws
(Fixing lower plate and main unit)
Heat insulation
The screw that fixed drain pan and
main unit is under this insulation.
Screws
(Fixing drain pan and vertical grille)
Screws
(Fixing louver drive member and main unit)
Louver
Louver
motor
motor
Screws
(Fixing louver motor and louver drive member)
– 102 –
www.ampair.co.uk | sales@ampair.co.uk
Remarks
5 -4
5 -5
5 -6
Vertical grille
6 -2
Louver drive
Louver drive
member
member
7 -3

Hide quick links: