Toshiba RAV-SM304MUT-E Service Manual page 53

Indoor unit digital inverter: compact 4-way cassette type; concealed duct type; ceiling type
Hide thumbs Also See for RAV-SM304MUT-E:
Table of Contents

Advertisement

[E04 error]
Does outdoor operate?
YES
Check indoor P.C. board.
Defect → Replace
[E10 error]
Is there no disorder of power supply?
Check indoor control P.C. board
(MCC-1402).
Defect → Replace
AMP Air Conditioning
NO
Is group address setup of
remote controller correct?
Are wiring in indoor unit and
1, 2, 3 inter-unit cables correct?
Are wirings of terminal blocks
(1, 2, 3) wired to CN67 normal?
Does the voltage
between 2 and 3 of the indoor unit
inter-unit terminal blocks
Check outdoor P.C. board.
Defect → Replace
YES
NO
YES
YES
YES
(1, 2, 3) vary?
∗ As shown in the following figure,
carry out measurement within 20 seconds
after the power was turned on.
Black
White
– 53 –
www.ampair.co.uk | sales@ampair.co.uk
NO
Check CODE No. [14].
NO
Correct wiring and
inter-unit cables.
NO
Correct wiring of connector
and terminal blocks.
NO
Check indoor P.C. board
(MCC-1402).
Defect → Replace
S5277G
3
2
1
Terminal block
Check power supply voltage.
Correct lines.
Check and eliminate noise, etc.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents