Control Specifications - Toshiba RAV-SM304MUT-E Service Manual

Indoor unit digital inverter: compact 4-way cassette type; concealed duct type; ceiling type
Hide thumbs Also See for RAV-SM304MUT-E:
Table of Contents

Advertisement

5-2. Control Specifications

No.
Item
1
When power
supply is reset
2
Operation
mode selection
3
Room temp.
control
AMP Air Conditioning
Outline of specifications
1) Distinction of outdoor unit
When the power supply is reset, the outdoors are distin-
guished and the control is selected according to the
distinguished result.
2) Setting of indoor fan speed and existence of air direction
adjustment
Based on EEPROM data, select setting of the indoor fan
speed and the existence of air direction adjustment.
1) Based on the operation mode selecting command from the
remote controller, the operation mode is selected.
Remote controller
command
STOP
FAN
COOL
DRY
HEAT
AUTO
• COOL/HEAT operation mode is
• The operation is performed as
1.0
Cooling thermo. OFF (Fan)
α
• Setup air volume
Ta˚C Ts +
–1.0
α
is corrected according to the outside temperature.
Outside temp.
No To
To ≥ 24°C
24°C > To ≥ 18°C
To < 18°C
To error
1) Adjustment range: Remote controller setup temperature ( °C )
Wired type
18°C to 29°C
Wireless type
18°C to 30°C
Control outline
Air conditioner stops.
Fan operation
Cooling operation
Dry operation
Heating operation
automatically selected by Ta, Ts
and To for operation.
shown in the following figure
according to Ta value at the first
time only. (In the range of Ts +
α
α
–1 < Ta < Ts +
+ 1, Cooling
thermo. OFF (Fan)/Setup air
volume operation continues.)
Cooling
operation
Heating
operation
α α α α α
Correction value (
0K
–1K
0K
+1K
0K
COOL/DRY
HEAT
18°C to 29°C
16°C to 30°C
– 27 –
www.ampair.co.uk | sales@ampair.co.uk
Remarks
Fan speed (rpm)/
Air direction adjustment
Ta: Room temp.
Ts: Setup temp.
To: Outside temp.
)
K = deg
AUTO
18°C to 29°C
17°C to 27°C