Toshiba RAV-SM304MUT-E Service Manual page 96

Indoor unit digital inverter: compact 4-way cassette type; concealed duct type; ceiling type
Hide thumbs Also See for RAV-SM304MUT-E:
Table of Contents

Advertisement

No.
Part name
Heat
12
exchanger
AMP Air Conditioning
Procedure
1. Detachment
1) Recover refrigerant gas.
2) Remove the refrigerant pipe at indoor unit
side.
3) Perform work of procedure 10 -1.
4) Take off screws (Ø4 × 10, 3 pcs.) fixing the
piping cover to remove the piping cover.
5) While holding the heat exchanger, remove
fixing band and fixing screws (Ø4 × 10, 3 pcs.)
and then remove the heat exchanger.
2. Attachment
1) Mount parts in order, heat exchanger
→ fixing band → piping cover → drain pan
→ bell mouth → electric parts box as original.
NOTE)
Arrange wires as original.
2) Attach the removed connectors and wires as
original.
3) Connect the refrigerant pipe as original, and
then perform vacuuming.
<Details of sensor lead wire drawing>
TCJ sensor
(Black)
TC sensor
(Red)
Wind pipe cover over the header,
attach a sensor on it.
(Do not set the head of tie wrap upward.)
Fixing band
– 96 –
www.ampair.co.uk | sales@ampair.co.uk
Remarks
Piping cover
Piping cover
3 screws
Fixing band for
heat exchanger
2 fixing screws for heat exchanger