Display; Parameter Tables - Resource Data Management PR0750-MOB Installation & User Manual

Mercury 2 & intuitive mercury mobile controller
Table of Contents

Advertisement

Mercury 2 & Intuitive Mobile Controller User Guide

Display

From the function menu scroll to and select diSP.
Press enter and one of the following values will be shown: -
0. Controller display will show the whole number and tenths value of a temperature reading. (Default)
1. Controller display will show temperatures as a whole number.

Parameter Tables

Number
Parameter
P-01
Cut-in Temp.
P-02
Cut In Differential
P-03
Control Weight
P-04
Display Weight
P-05
Lag Comp Delay
P-06
Anti SC Time
P-07
Lag Cut Out Diff
P-85
Key-switch Mode
P-87
Control Probe type
P-90
Resistor Case Off
P-92
Fans temperature mode
P-93
Fans Off Temperature
P-15
Probe 5 Select
P-16
Relay 3 Mode
P-29
Probe 3 Resistor function
P-18
Service Interval time
P-19
Switch Resistors
P-98
Lights Case Off
P-99
Load Shedding
P-30
Do (enable) Discharge Stop Compressor A
P-31
Do (enable) Discharge Stop Compressor B
P-32
Discharge Stop Value
P-33
Discharge Stop Differential
P-34
Maximum Compressor Run Time
P-35
Comp Stop Both
P-20
Alarm Delay
P-21
UT Alarm
P-22
OT Alarm
P-23
Log Probe Type
P-24
Slug Log Probe
P-25
Log Alarm Delay
P-26
Log UT Alarm
P-27
Log OT Alarm
P-28
Monitor OT Alarm
P-40
Defrost Mode
P-41
Defrost Start
P-42
Defrosts per Day
P-43
No Defrost Time
P-44
Def Terminate Temp.
Warning
Ensure that all power is
switched off before
installing or maintaining
this product
Please Note
This function is now complete
Range
o
o
C
(
F )
-42 to 30 (-43.6 to 86)
0 to 10 (0 to 18)
0 to 100
0 to 100
00:00 to 15:00
00:00 to 15:00
0 to 10 (0 to 18)
0 = Case Off
1 = Fans only
2 = toggle
0 = Use Air on Probe
1 = Use Log Probe
0 (Disabled),1(Enabled)
0 = Off
1 = Temperature
2 = Over-temperature
3 = Temp/OT
-42 to 30 (-43.6 to 86)
0 = Defrost, 1 = Monitor
0 = Lights, 1 = Alarm
0 = Plant fault,
1 = External defrost
0 to 128
0 (Off), 1(On)
0 (Off), 1 (On),
2 (Unused)
0 (Off), 1 (Mode 1),
2 (Mode 2)
0 (Off), 1(On)
0 (Off), 1(On)
-49 to 128
-42 to 30
00:00 to 99:00
0 = Yes
1 = No
00:00 to 99:00
-49 to 60 (-56.2 to 140)
-49 to 60 (-56.2 to 140)
0 (Off), 1 (Logging),
2 (Logging/Alarm)
0 (Off), 1 (On)
00:00 to 99:00
-49 to 60 (-56.2 to 140)
-49 to 60 (-56.2 to 140)
-49 to 60 (-56.2 to 140)
0 (Local), 1 (Remote),
2 (External)
00:00 to 23:59
0 to 8
0 to 25
-42 to 30 (-43.6 to 86)
Revision 1.1
Step
Units
Default LT
o
o
C (
F )
0.1
Deg
-20 (-4)
0.1
Deg
2.5 (4.5)
1
%
40
1
%
40
00:05
mm:ss
00:40
00:05
mm:ss
07:00
0.1
Deg
2.5 (4.5)
1
0
1
0
0
1
0
0.1
Deg
-10 (14)
1
0
1
0
1
0
1
KHrs
60
1
0
1
0
1
0
1
0
0.1
Deg
55
0.1
Deg
10
01:00
mm:ss
00:00
1
0
01:00
mm:ss
20:00
0.1
Deg
-30 (-22)
0.1
Deg
-15 (5)
Off
Off
01:00
mm:ss
20:00
0.1
Deg
-35 (-31)
0.1
Deg
-12 (10.4)
0.1
Deg
20 (68)
Local
00:01
hh:mm
01:00
1
6
1
hours
12
0.1
Deg
14 (57.2)
Page 9 of 21
www.resourcedm.com
Default HT
o
o
C (
F )
3.5 (38.3)
2.5 (4.5)
30
30
00:10
07:00
2.5 (4.5)
0
0
0
0
8 (46.4)
0
0
0
60
1
0
0
0
0
55
10
00:00
0
20:00
-2 (28.4)
5 (41)
Off
Off
20:00
-1 (30.2)
6 (42.8)
20 (68)
Local
01:00
6
12
10 (50)