Mercury 2 & Intuitive Mobile Controller User Guide

Fans Only "FAnS"

Selecting the Fans Only option will put the controller into the Fans Only state if the current state is not Fans Only. If the current state is
Fans Only then the controller will change to the Normal state. Selecting this option will exit the setup menu automatically. The display will
show "FAnS OnLy"
If a remote display with key switch is being used, this function can be invoked by turning the key switch to the fans only position (90
degrees clockwise) with parameter P85 set to "fans"

Case Off "CASE"

Selecting the Case Off option will put the controller into the Case Off state if the current state is not Case Off. If the current state is Case
Off then the controller will change to the Normal state. Selecting this option will exit the setup menu automatically. The display will show
"CASE OFF". An alarm is generated, fixed delay of 1 minute, when the controller is placed into the Case Off state.
If a remote display with key switch is being used, this function can be invoked by turning the key switch to the case-off position.
(Clockwise 90 degrees) with parameter P85 set to "case".

Lights Only "Ligt"

Selecting the Lights Only option will put the controller into the Lights Only state if the current state is not Lights Only. If the current state is
Lights Only then the controller will change to the Normal state. Selecting this option will exit the setup menu automatically. The display
will show "LitS OnLy"
Note. When lights are being used in "Remote" mode with a timing channel: -
If the controller goes offline, the lights are turned ON after a delay of 5 minutes. The lights will stay on until the controller comes back on-
line where they will revert to the state of the timing channel being used.

Probe Offset

This feature allows each probe value to be modified by an "offset". Offset values are from -10
channel basis. Example C1 = Probe 1.

Remote Commands

The following commands can be used by a Data Builder program: -
Command
Defrost Command
Defrost Command
Setpoint Command
Case Off Command
Haccp Command
Button Command
Use an "Analogue Out" block configured to the
controller name and in the value field type in the
command you require. Use a "Setting block" as
the input to the "Analogue Out" block to send the
Value.
See Example on the right, which increases the
setpoint by 10 degrees.
Warning
Ensure that all power is
switched off before
installing or maintaining
this product
Please Note
Value to send
Description
1
Initiates a defrost cycle
3
Terminates the defrost
+/-18
Is added to or subtracted from the setpoint
5
Sets the controller to Case Off
0
Restores the controller from Case Off to Normal
0
HACCP LED OFF
1
HACCP LED On
2
HACCP LED Flashes
0
Buttons backlights Off
1
Buttons backlights On
2
Buttons Backlights Flash
O
C (-18
Revision 1.1
www.resourcedm.com
O
O
O
F) to +10
C (+18
F) and on a
Conditions
Defrost mode: remote
Defrost mode: remote
Defrost hold: On
Defrost min state complete
Page 17 of 21