Mercury 2 & Intuitive Mobile Controller User Guide
P-45
Def Min Time
P-46
Def Max Time
P-47
Drain Down
P-48
Recovery Time
P-89
Pump Down Time
P-86
Fan Delay mode
P-49
Fan Delay Time
P-88
Fan Delay Temp
P-50
Fans In Defrost
P-91
Defrost Type (Integral)
P-94
Defrost Hold
P-95
Defrost Skip
P-96
Defrost Skip Time
P-60
Lights Mode
P-61
Sun Lights On
P-62
Sun Lights Off
P-63
Mon Lights On
P-64
Mon Lights Off
P-65
Tue Lights On
P-66
Tue Lights Off
P-67
Wed Lights On
P-68
Wed Lights Off
P-69
Thu Lights On
P-70
Thu Lights Off
P-71
Fri Lights On
P-72
Fri Lights Off
P-73
Sat Lights On
P-74
Sat Lights Off
dFLt
Restore defaults

Parameter Descriptions

Number
Parameter
P-01
Cut-in Temp
P-02
Diff
P-03
Control Weight
P-04
Display Weight
P-05
Lag Comp Delay
P-06
Anti SC Time
P-07
Lag Cut Out Diff
P-85
Key-switch Mode
P-87
Control Probe type
P-90
Resistor Case Off
P-92
Fans temperature
mode
P-93
Fans Off Temperature
Warning
Ensure that all power is
switched off before
installing or maintaining
this product
Please Note
00:00 to 99:00
00:00 to 99:00
00:00 to 24:00
00:00 to 99:00
00:00 to 99:00
0 = Time 1 = Temp
00:00 to 99:00
-42 to 30 (-43.6 to 86)
0 (Off), 1 (On)
0 = Elec. 1 = Gas.
2 = Elec CIn
0 (Off), 1 (On)
0 (Off), 1 (On)
00:00 to 99:00
0 (Local), 1 (Remote),
2 (Man Off), 3(Man On)
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
00:00 to 23:59
Description
Temperature at which the lead compressor will switch on.
Differential temperature below the cut-in temperature. The lead compressor switches off when below this
temperature
Percentage of the Air-On temperature that is used to calculate the control temp. The remaining
percentage will be used on the Air-Off temperature
Example, P-03 set to 30%
Control temp = 30% Air-on + 70% Air-off
As above only applied to the display temperature
Delay before the second compressor is switched on if the temperature is still above set-point.
Note – The lead and lag compressors swap after each defrost to even the run times.
Allows the user to set the compressor for a given number of starts/hour
Diff below the Cut-In Temp the lag compressor switches off.
Single Compressor Operation
To disable compressor B operation and use only a single compressor for control set parameter P-07 to 0.
This will allow the controller work with just one compressor (A) and ignore compressor B.
Allows the keys switch to be: -
Single turn for case off (Case off mode)
Single turn for Fans only (Fans Mode)
Single turn for case off, double turn for fans only (Toggle mode)
Switches between using the air-on probe and the Logging probe. Note the control and display
temperature will still be a derivative of the weighted
Average of the control probe + Air-off probe
Turns on/off the switched resistor case off function
Allows the user to set the fans to turn off when: -
A pre-determined temperature is reached (P93)
When an over-temperature alarm is present
When either P93 is reached or an OT alarm is present
Temperature for the above (P92) operation. Note the defrost termination probe is the source of the
temperature reading used in this feature. If the defrost termination probe isn't fitted then a similar process
to P-44 is used.
Revision 1.1
01:00
mm:ss
05:00
01:00
mm:ss
30:00
00:15
mm:ss
01:30
01:00
mm:ss
30:00
01:00
mm:ss
00:00
1
0
01:00
mm:ss
00:00
0.1
Deg
-20 (-4)
On
0
Off
Off
01:00
mm:ss
12:00
Local
00:01
hh:mm
08:00
00:01
hh:mm
20:00
00:01
hh:mm
08:00
00:01
hh:mm
20:00
00:01
hh:mm
08:00
00:01
hh:mm
20:00
00:01
hh:mm
08:00
00:01
hh:mm
20:00
00:01
hh:mm
08:00
00:01
hh:mm
20:00
00:01
hh:mm
08:00
00:01
hh:mm
20:00
00:01
hh:mm
08:00
00:01
hh:mm
20:00
Page 10 of 21
www.resourcedm.com
05:00
30:00
00:30
30:00
00:00
0
00:00
0.0 (32)
On
0
Off
Off
12:00
Local
08:00
20:00
08:00
20:00
08:00
20:00
08:00
20:00
08:00
20:00
08:00
20:00
08:00
20:00