KROHNE BM 70 A Installation And Operating Instructions Manual page 54

Level, non-contact level gauging using electromagnetic waves
Table of Contents

Advertisement

Switching output
characteristics
Sw.output application
Examples
see Sect. 8.5
Error message
Contact opens
when error occurs
Contact closes
when error occurs
Limit value, level
- Contact closes when
upper limit exceeded
- Contact closes when
lower limit exceeded
Limit value, distance
- Contact closes when
upper limit exceeded
- Contact closes when
lower limit exceeded
Limit value, conversion
- Contact closes when
upper limit exceeded
- Contact closes when
lower limit exceeded
Limit value, reflection
- Contact closes when
upper limit exceeded
- Contact closes when
lower limit exceeded
e.g. operation indicator
Contact closed when
supply power applied
and open at power fail
Installation and operating instructions BM 70 A/P
FUNCTION S:
LEVEL
Fct. 3.6.1
DISTANCE
CONVERSION
REFLECTION
THRESHOLD
Fct 3.6.3
TYPE S
Fct. 3.6.2
Switching output
HIGH
open
closed
LOW
closed
open
Switching function
settable by way of ...
Fct. 3.6.1
Fct. 3.6.2
FUNCTION S
TYPE S
ERROR
no *
OPEN
ERROR
no *
CLOSED
LEVEL
HIGH
LEVEL
LOW
DISTANCE
HIGH
DISTANCE
LOW
HIGH
CONVERSION
CONVERSION
LOW
REFLECTION
HIGH
REFLECTION
LOW
OFF
no *
Overflow
= Threshold + Hysteresis / 2
HYSTERESIS
Fct. 3.6.4
Underflow
= Threshold + Hysteresis / 2
open
closed
closed
open
Further parameters
settable via ...
Fct. 3.6.3
Fct. 3.6.4
THRESHOLD
HYSTERESIS
no *
no*
no *
no*
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
no *
no *
Page: 54
* Setting has no effect on the
function of the switching output!
Overflow =
Measured value higher than limit
value
(= threshold plus hysteresis / 2)
Underflow =
Measured value lower than limit
value
(= threshold minus hysteresis / 2)
11/00