B) Stilling well or Wave-Guide
A stilling well or Wave-Guide may be mounted in any position on the tank.
(For design layout: see also Section 6.1.4; for block distance: see Section 3.3).
Stilling well application
A stilling well or Wave-Guide
is positively recommended for
horizontal cylindrical tanks
(to avoid multiple reflections):
6.1.3 Mounting on tank fitting
A) Horn antenna
Should be mounted on the tank fitting as close to the horizontal as possible (deviation < ± 2°).
Exception: if product surface is not horizontal, (e.g. particulate materials) the flange can be aligned
roughly parallel to it.
The antenna should project out of the fitting:
Tank nozzle
Installation and operating instructions BM 70 A/P
In a side vessel
L
D
BM 70 A Wave-Guide
Antenna
Diameter D
Type 4
200 mm (8")
Type 3
140 mm (5.5")
*
Hastelloy: + 30 mm (1.2")
(subject to change without notice)
Page: 19
Length l*
335 mm (13.2")
223 mm (8.8")
11/00