Table Of Contents; Safety Precautions; Accessories; Electrical Requirement - Fujitsu UTY-RNN*M series Installation Manual

Air conditioner remote controller (wired type)
Table of Contents

Advertisement

INSTALLATION MANUAL
PART NO. 9373328162-04
AIR CONDITIONER REMOTE CONTROLLER
(WIRED TYPE)
Contents
1. SAFETY PRECAUTIONS .............................................. 1
2. ACCESSORIES ............................................................. 1
3. ELECTRICAL REQUIREMENT ...................................... 1
4.1. Dimensions ............................................................. 2
4.2. Name of parts ......................................................... 2
5.1. Installation .................................................................. 3
5.2. Setting the DIP switch ............................................ 3
6.1. Group control .......................................................... 4
6.2. Dual remote control ................................................ 4
7. TURNING ON THE POWER .......................................... 5
DETECTION LOCATION .................................................. 5
9. FUNCTION SETTING .................................................... 5
10. TEST OPERATION ........................................................ 7
11. ERROR CODES ............................................................ 8

1. SAFETY PRECAUTIONS

Let the customer keep this installation manual because it is needed
when the air conditioner or remote controller is serviced or moved.
This mark indicates procedures which, if improp-
WARNING
erly performed, might lead to the death or serious
injury of the user.
For the air conditioner to operate satisfactorily, install it as outlined in
this installation manual.
Installation work must be performed in accordance with national wiring
standards by authorized personnel only.
Do not turn on the power until all installation work is complete.
This mark indicates procedures which, if improp-
CAUTION
erly performed, might possibly result in personal
harm to the user or damage to property.
When detecting the room temperature using the remote controller,
please set up the remote controller according to the following
conditions. If the remote controller is not located properly, the correct
room temperature will not be detected, and thus abnormal conditions
like "not cooled" or "not heated" will occur even if the air conditioner is
running normally.
Locate where an average temperature
for the room being air-conditioned will be
sensed.
Do not locate directly exposed to the outlet
air from the air conditioner.
Locate out of direct sunlight.
Locate away from the infl uence of other
heat sources.
Do not touch the remote controller PC board and
PC board parts directly with your hands.
Do not wire the remote controller cable and the bus wire together with
or parallel to the connection cables, transmission cables, and power
supply cables of the indoor and outdoor units. It may cause erroneous
operation.
When installing the bus wire near a source of electromagnetic waves,
use shielded wire.
Do not set the DIP switches, either on the air conditioner or the remote
controller, in any way other than indicated in this manual or the manual
that is supplied with the air conditioner. Doing so may result in an
improper operation.
En-1

2. ACCESSORIES

The following installation parts are supplied. Use them as required.
Installation manual
Operating manual
Remote controller cable
Connecting cable
Tapping screw (M4 x 16mm)
Binder
Tapping screw (M4 x 14mm)
Cable clamper

3. ELECTRICAL REQUIREMENT

When connecting the remote controller use the following wiring.
* We recommend that you purchase our service parts for the remote control-
ler cable. Contact service personnel to purchase this.
Temperature sensor
Name and Shape
Q'ty
1
1
1
1
2
1
1
1
Cable
Cable size
22AWG
Remote controller
Sheathed PVC cable,
cable
Polar 3 core
Application
This manual
Instruction book for operation
For connecting the remote
controller
For connecting the remote control-
ler cable to the wall mounted type
and the fl oor type indoor unit
For installing the remote controller
For remote controller and remote
controller cable binding
For installing the remote controller
cable to the indoor unit
For installing the remote controller
cable to the indoor unit
Remarks
Use Sheathed PVC
cable in accordance with
local rules for cable.