Clock Settings; Line 4 - IVT GreenlineC Manual To Installation, Commissioning And Maintenance

Table of Contents

Advertisement

Line 4

Main menu
Timer control
settings
Return
Select
Clock setting
Clock setting HP
accord. to clock 4.1
Return
Select
Clock setting HP
Mo
00:00-00:00
Return
Adjust
Clock setting HP
Mo
00:00-
00:00
^^
Cancel
Clock setting HP
Mo
22:00-06:00
^^
Cancel
<-
Clock setting HP
Mo
22:00-06:00
Return
Adjust
Clock setting
Setting level
heat pump +/-
Return
Select
Clock setting
Clock setting DHW
accord. to clock 4.3
Return
Select
4
1
1
->
1
->
1
4.1.1
Not
operating
mode C
You have now moved to timer control settings line 4.
Here you can set the times day for day that you want to
utilise the clock settings. You can set all the weekdays
independent of each other. Press "Select".
The example describes how you set Monday between 22:00
and 06:00. Press "Adjust".
There is now a cursor under Monday. Turn the knob and mo
becomes Mo. Monday is now activated.
Now set the clock setting for between 22:00 and 06:00 in
the morning. Press the right arrow button until the cursor is
under the first 00. Turn the knob until 22:00 appears. Press
the button twice more (the cursor moves two steps to the
right) and turn the knob until 06:00 appears. Press the right
arrow button once more and the arrow is replaced by Save.
Press "Save" to set the timer controls.
You can now do the same for all the other days of the week
you want to timer control. Use the knob in this display to
come to the other days.
In display 4.1.1 you set how much you want the temperature
to be raised or lowered in the above time zone settings. If
you choose for example -5°C, the heating system tempera-
ture is lowered by 5°C.
In display 4.3 you can disconnect the hot water completely
during e.g. peak rate times. This is done in the same way as
with the heat pump time controls.
16