11-Series I/O Module Parameters - Allen-Bradley PowerFlex 750 Series Programming Manual

Hide thumbs Also See for PowerFlex 750 Series:
Table of Contents

Advertisement

Chapter 5
Embedded Feature and Option Module Parameters
11-Series I/O Module
Parameters
No.
Display Name
Full Name
Description
1
Dig In Sts
Digital Input Status
Status of the digital inputs.
Options
Default 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
2
Dig In Filt Mask
Digital Input Filter Mask
Filters the selected digital input.
Important: Only used by 11-Series I/O Module models 20-750-1133C-1R2T and 20-750-1132C-2R. (Modules with 24V DC inputs.)
Options
Default 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
3
Dig In Filt
Digital Input Filter
Sets the amount of filtering on the digital inputs.
Important: Only used by 11-Series I/O Module models 20-750-1133C-1R2T and 20-
750-1132C-2R. (Modules with 24V DC inputs.)
No.
Display Name
Full Name
Description
5
Dig Out Sts
Digital Output Status
Status of the digital outputs.
Options
Default 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
(1) Bit 1 = "Trans Out 0" for 11-Series I/O Module model 20-750-1133C-1R2T
= "Relay Out 1" for 11-Series I/O Module models 20-750-1132C-2R and 20-750-1132D-2R
(2) Bit 2 is only used by 11-Series I/O Module 20-750-1133C-1R2T
242
Rockwell Automation Publication 750-PM001N-EN-P - February 2017
Values
0 = Input Not Activated
1 = Input Activated
0 = Input Not Filtered
1 = Input Filtered
Units:
mS
Default:
4
Min/Max:
2 / 10
Values
0 = Output De-energized
1 = Output Energized
RO 16-bit
Integer
RW 16-bit
Integer
RW 32-bit
Integer
RO 16-bit
Integer