About Parameters - Allen-Bradley PowerFlex 750 Series Programming Manual

Hide thumbs Also See for PowerFlex 750 Series:
Table of Contents

Advertisement

Chapter 2
Parameter Organization

About Parameters

No.
Display Name
Full Name
Description
28
Motor NP RPM
Motor Nameplate Revolutions Per Minute
Rated RPM shown on the motor nameplate.
107
Trq Adapt En
Torque Adaption Enable
Enables or disables the adaptive torque calculation. This selection is active only in motor
control mode flux vector induction (P35 [Motor Ctrl Mode] = 3 "Induction FV").
164
DI Run Forward
Digital Input Run Forward
Assigns a digital input used to run the drive (2 wire control) and command forward
direction.
753
220
Digital In Sts
Digital Input Status
Status of the digital inputs resident on the main control board (Port 0).
Options
Default 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
20
To configure a drive module to operate in a specific way, certain drive parameters
may have to be configured appropriately. Three types of parameters exist:
• Numeric Parameters
These parameters have a single numeric value (such as 1750.0 RPM).
• ENUM Parameters
These parameters allow a selection from 2 or more items. The LCD HIM
displays a text message for each item.
• Indirect Parameters
These parameters, represented by a maximum value of 159999 or
159999.15, are used to create assignments or to select either a data source
or destination. The first two digits are used to select a port. The next four
digits select a parameter number. If applicable, the two digits following the
decimal point select a bit. For example, to assign an I/O option module in
port 4 using a run contact on digital input 0, parameter 163 [DI Run] is set
to 040001.00.
• Bit Parameters
These parameters have individual bits associated with features or
conditions. If the bit is 0, the feature is off or the condition is false. If the
bit is 1, the feature is on or the condition is true.
Table 3
shows how each parameter type is presented in this manual.
Table 3 - Table Explanation
Rockwell Automation Publication 750-PM001N-EN-P - February 2017
Values
Units:
RPM
Default:
1750.0
Min/Max:
1.0 / 40000.0
Default:
1 = "Enabled"
Options:
0 = "Disabled"
1 = "Enabled"
Default:
0.00
Min/Max:
0.00 / 159999.15
0 = Condition False
1 = Condition True
RW Real
RW 32-bit
Integer
RW 32-bit
Integer
RO 16-bit
Integer