Flue Collar Orientation; Flue Collar Heat Shield; Chimney Connector - Jøtul F 45 Greenville Installation And Operating Instructions Manual

Table of Contents

Advertisement

139575 Rev_08 F 45 9/17

1.5 Flue Collar Orientation

The Flue Collar is oriented in the Top Exit position. To
change orientation to Rear Exit:
1. Remove the Rear Shroud from the stove with removal of
the four sheet metal screws at the top and bottom of the
shroud sides.
2. Twist and remove the perforated cut-out section from
the top edge of the rear shroud.
3. Use a 10 mm socket wrench to remove the two M6 nuts
and bolts that attach the flue collar to the stove. Orient
the flue collar to the rear and use the same nuts and
bolts to re-attach it to the stove.
4. Reattach the shroud to the back of the stove using the
sheet metal screws previously removed.

1.6 Flue Collar Heat Shield

Not applicable for rear exit configuration.
1. Fold the heat shield on the perforations to conform to
the shape as illustrated in fig.2.
2. Secure it to the rear stove shroud using the four #8 x 12
sheet metal screws from the hardware bag.

1.7 Chimney Connector

Use 6" single wall or listed 6" double-wall stovepipe to
connect the stove to the chimney. Single wall stovepipe
must be black steel or stainless steel and have a minimum
thickness of 24 gauge. Do not use aluminum or galvanized
steel pipe for chimney connection - these materials are not
suitable for use with solid fuel.
Follow these guidelines:
• Do not use chimney connector as a chimney. It is
intended only as a connection device.
• Each connector section must be oriented with the male
(crimped) end pointing toward the stove. See fig. 3.
• Secure all connector joints with three sheet metal
screws. The connection to the stove flue collar uses the
two M6x 16 mm self-tapping screws provided.
• For the best performance, the chimney connector should
be as short and direct as possible, including no more
than two 90° elbows.
• The maximum vertical run of single wall stovepipe
should not exceed 10 ft. (305 cm).
• The maximum horizontal run should not exceed 3 ft.
(92 cm) with a 1/4" rise per foot. Under no circumstance
should horizontal pipe be installed slanting down
toward the chimney.
6
Figure 2. Flue Collar heat shield attachment.
Toward
Stove
Figure 3. Chimney connector orientation.
• No part of the chimney connector may pass
through an attic or roof space, closet or other
concealed space, or through a floor or ceiling.
All sections of the chimney connectors must be
accessible for cleaning. Where passage through
a wall or partition of combustible construction is
desired, the installation must conform with NFPA
211 or CAN/CSA-B365, and is also addressed in this
manual.
• Do not connect this stove to a chimney flue
serving another appliance.
Flue Gas
Direction

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents