Step 2: Exemplary setting for parallel mode
In this example, the master is configured according to factory settings.
The slaves do not require setting!
Master
DS-8 Ch. voltage(GEL 14,4V)
DS-7 Ch. voltage(GEL 14,4V)
DS-6 Absorption time (8 h)
DS-5 Adaptive charging (on)
DS-4 Dyn. current limit (off)
DS-3 UPS function (on)
DS-2 Voltage (230V)
DS-1 Frequency (50Hz)
To store the settings after the required values have been set: press the 'Down' button
of the master for 2 seconds (lower button to the right of the DIP switches). The
temperature and low-battery LED's will flash to indicate acceptance of the
settings.
You can then leave the DIP switches in the selected positions, so that the 'other
settings' can always be recovered.
To start the system: first, turn all devices off. The system will start up as soon
as all devices have been turned on.
Step 2: Exemplary setting for 3-phase mode
In this example the leader is configured according to factory settings.
Leader (L1)
DS-8 Ch. Volt. GEL 14,4V
DS-7 Ch. Volt. GEL 14,4V
DS-6 Absorption time (8 h)
DS-5 Adaptive ch. (on)
DS-4 Dyn. current limit (off)
DS-3 UPS function (on)
DS-2 Voltage (230V)
DS-1 Frequency (50Hz)
To store the settings after the required values have been set: press the 'Down' button
of the leader for 2 seconds (lower button to the right of the DIP switches). The
temperature and low-battery LED's will flash to indicate acceptance of the
settings.
You can then leave the DIP switches in the selected positions, so that the 'other
settings' can always be recovered.
34
off
DS-8 na
on
DS-7 na
on
DS-6 na
on
DS-5 na
off
DS-4 na
on
DS-3 na
on
DS-2 na
on
DS-1 na
Follower (L2)
off
DS-8 na
on
DS-7 na
on
DS-6 na
on
DS-5 na
off
DS-4 D. c. l. (off)
on
DS-3 UPS f. (on)
on
DS-2 V (230V)
on
DS-1 na
Slave 1
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 na
DS-1 na
DS-8 na
DS-7 na
DS-6 na
DS-5 na
off
DS-4 D. c. l. (off)
on
DS-3 UPS f. (on)
on
DS-2 V (230V)
DS-1 na
Slave 2
Follower (L3)
off
on
on