Siemens SIMATIC S7-300 FM 350-1 Manual page 123

Counter
Table of Contents

Advertisement

Single Setting with DI Set
The following figure shows single setting of the counter with digital input DI Set. In the case
represented here, only ENSET_UP is set, i.e., the counter is set during up counting.
With the first rising pulse edge at digital input DI Set, the counter is set provided that
ENSET_UP is similarly set. If you want to set the counter again, you must first reset
ENSET_UP and then set it again. The next positive pulse edge at digital input DI Set will
then result in the counter being set.
Figure 7-23
Single Setting with DI Set
Multiple Setting with DI Set
The following figure shows multiple setting of the counter with DI Set. In the case
represented here, only ENSET_UP is set, i.e., the counter is set during up counting.
With every rising pulse edge at digital input DI Set, the counter is set provided that
ENSET_UP is similarly set. If you reset ENSET_UP, the counter will not be set by DI Set.
Only when you have set ENSET_UP again, will the next positive edge at DI Set result in the
setting of the counter.
Figure 7-24
Multiple Setting with DI Set
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
Operating Modes, parameters and commands
7.3 Count modes
123