Programming the FM 350-1
5.7 Programming FM 350-1 without FCs
5.7.3

Control interface for measuring modes

Control interface for measuring modes
Parameter LOAD_VAL (bytes 0 to 3) has two different meanings:
● You set bit L_PREPAR to define the LOAD_VAL parameter as a low limit.
● You set bit C_DOPARA bit in byte 0 to define the reaction at output DO0.
Table 5- 16
Control interface for measuring modes (outputs)
Offset to the start
Parameter
address
Bytes 0 to 3
LOAD_VAL
Byte 0
LOAD_VAL
Byte 1
Byte 2
Byte 3
Bytes 4 to 7
CMP_V1
Bytes 8 to 9
CMP_V2
Bytes 10 to 11
Byte 12
NEUSTQ
OT_ERR_A
Byte 13
SW_GATE
GATE_STP
62
Assignment
Load low limit with bit L_PREPAR
Define reaction of DO0 at bit C_DOPARA
Bits 2 to 7
Bit 1
Bit 0
Irrelevant
0
0
Irrelevant
0
1
Irrelevant
1
0
Irrelevant
1
1
Reserve = 0
Reserve = 0
Reserve = 0
High limit; load with bit T_CMP_V1
Update time; load with bit: T_CMP_V2
Bit 7: Reserve = 0
Bit 6: Restart acknowledgement
Bit 5: Reserve = 0
Bit 4: Reserve = 0
Bit 3: Operator error acknowledgement
Bit 2: Reserve = 0
Bit 1: Reserve = 0
Bit 0: Reserve = 0
Bit 7: Reserve = 0
Bit 6: Reserve = 0
Bit 5: Reserve = 0
Bit 4: Reserve = 0
Bit 3: SW gate control bit
Bit 2: General gate stop
Bit 1: –
Bit 0: –
Reaction of output DO0
No comparison
Out of limits
Below the low limit
Above the high limit
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01