Counter
Table of Contents

Advertisement

Pin Assignments of the Front Connector
Table 3- 1
Pin assignments of the front connector
Connection
Name
Auxiliary voltage
1
1L+
2
1M
3
1M
4
5.2 VDC
5
24 VDC
6
A A*
7
/A
8
B B*
9
/B
10
N N*
11
/N
12
Digital Inputs and Digital Outputs
13
I0
14
I1
15
I2
16
17
Q0
18
Q1
Load voltage
19
2L+
20
2M
Note
The circuits for the counter inputs (encoder supply, encoder signals) are non-isolated to the
ground of the CPU, that is, terminal 2 (1M) must have a low-resistance connection to CPU
ground. If this connection does not exist, a malfunction or a defect of the FM 350-1 can
result.
If you supply the encoders externally, you must also connect the ground of this external
voltage with the ground of the CPU.
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
Input /
Function
Output
ON
ON
5 V encoder RS 422,
symmetric
OFF
OFF
OFF
ON
Encoder signal A
ON
Encoder signal /A
ON
Encoder signal B
ON
Encoder signal /B
ON
Encoder signal N
ON
Encoder signal /N
ON
ON
ON
OFF
OFF
ON
ON
3.1 Pin assignments of the front connector
24 V auxiliary voltage
Auxiliary voltage ground
24 V encoder,
asymmetric
Encoder supply ground
Encoder power supply 5.2 V
Encoder power supply 24 V
Encoder signal B *
Encoder signal N *
Digital input DI Start
Digital input DI Stop
Digital input DI Set
Digital output DO0
Digital output DO1
24 V load voltage
Load voltage ground for the digital inputs and outputs
Wiring the FM 350-1
24 V pulse encoders
with direction level
Encoder signal A *
Directional signal
24 V initiator