Gas Piping - IBC SL 14-115 G3 Installation And Operating Instructions Manual

Modulating gas boilers
Table of Contents

Advertisement

NOTE
It is essential to check gas
supply pressure to each
boiler with a manometer or
other high-quality precision
measuring device. Pressure
should be monitored before
firing the boiler, when the
regulator is in a "lock-up"
condition and during operation,
throughout the boiler's full
modulation range.
Pay special attention to retrofit
situations where existing
regulators may have an over-
sized orifice and/or worn seats,
causing pressure "creep" and
high lock up pressures.
MODEL
SL 14-115 G3 (Natural Gas)
SL 14-115 G3 (Propane)
SL 20-160 G3 (Natural Gas)
SL 20-160 G3 (Propane)
SL 30-199 G3 (Natural Gas)
SL 30-199 G3 (Propane)
1-30
SL 20-115 G2 MODULATING GAS BOILER
SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS
Figure 42: Multiple boiler low loss header piping concept

1.7 GAS PIPING

The boiler requires an inlet gas pressure of at least 4.0" w.c. for natural gas or propane.
For either fuel, the inlet pressure shall be no greater than 14.0" w.c. Confirm this pressure
range is available with your local gas supplier.
The inlet gas connection of the boiler's gas valve is 1/2" NPT (female).
Adequate gas supply piping shall be provided with no smaller than a 1/2" Iron Pipe Size
(e.g. Iron Pipe Size (IPS) and using a 1" w.c. pressure drop, in accordance with the
following chart:
1/2" IPS
30'
90'
10'
50'
10'
30'
Table 6: Maximum Pipe Length (ft) Schedule 40 steel
3/4" IPS
1" IPS
125'
350'
70'
200'
40'
125'
INSTALLATION AND OPERATION INSTRUCTIONS
1-1/4" IPS
400'
1,000'
200'
600'
150'
600'
400'
1,600'

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sl 20-160 g3Sl 30-199 g3

Table of Contents