Rish EM 3490 SS Installation & Operating Instruction

Single phase energy meter

Advertisement

Quick Links

EM 3490 SS
Single Phase Energy Meter
Installation & Operating Instructions
Section
Contents
1.
Introduction
2.
Measurement Reading Screen
3.
Phase Indications
4.
4.2.1.1 Potential transformer Primary value
4.2.1.2 Potential transformer secondary value
4.2.1.3 Current transformer Primary value
4.2.1.4 Energy Display on modbus
4.2.1.5 Energy Digit Rollover(reset) count
4.2.2.3 RS 485 Parity selection
4.2.3 Reset Parameter selection screen
4.2.3.1 Resetting Parameter
4.2.4 Relay Output parameter selection screen
4.2.4.1 Pulse Duration (width) selection
4.2.4.2 Pulse rate divisor
4.2.5 Quit screen
5.
6.
7.
8.
8.2
Case Dimensions and Panel Cut-out
8.3
9.
10.
Specification
Connection for Optional Pulse output / RS 485
11.
15000251_Rev.C - 12/ 08
1. Introduction
The instrument is a panel mounted 96 x 96mm DIN Quadratic energy
meter. It accumulates Active energy, in single phase network.
The instrument also measures AC Voltage, AC Current, Frequency,
Power, Power factor, Phase Angle, Apparent Energy which can be accessed via
Modbus. All voltage & Current measurements are True RMS upto 15th harmonic.
Ultra high brightness LED display.
Meter can be configured & Programmed at site
for the following :
PT Primary, PT Secondary, CT Primary, Modbus
Settings & Pulse output settings.
x1000
kWh
V
I
ON
REV
The front panel has two push buttons through
which the user can reset the energy & configure
the product.
3600 Imp/KWh
The front panel has Impulse red led, flashing at
rate proportional to measured power.
Its impulse rate is 3600impulses/kWh.
Down
Up
TABLE 1:
Measured Parameters
Units of measurement
Display Parameter
kWh
Modbus Parameter
System Voltage
Volts
Amps
System Current
Frequency
Hz
Kwatts
KVAr
KVA
Power Factor
Phase Angle
Degree
Active Energy
Wh
Apparent Energy
VAh
2. Measurement Reading Screen
In normal operation the user is presented with active energy measurement screen.
Screen 1 : Active Energy (kWh)
x1000
kWh
V
ON
I
REV
3600 Imp/KWh
Active energy is displayed in 8 digit counter with auto ranging feature. Below given table
describes auto ranging with minimum resolution of energy measured in perticular range.
When x1000 LED glows the energy is displayed in mega watt.
Display Format
X1000 LED
Minimum resolution
99.999999
OFF
1 miliWatt
999.99999
OFF
10 miliWatt
9999.9999
OFF
100 miliWatt
99999.999
OFF
1 Watt
999999.99
OFF
10 Watt
9999999.9
OFF
100 Watt
99999999
OFF
1 kiloWatt
999999.99
ON
10 kiloWatt
9999999.9
ON
100 kiloWatt
99999999
ON
1 MegaWatt
Maximum Active energy count reached is 99999999 MegaWatt after this counter
rollovers to zero and measurement starts from first range.
Impulse led on front panel can be used to cross check the energy calibration on site.
Its nominal impulse rate is 3600 impulses / kWh.
1
3. Phase Indications
x1000
kWh
V
I
ON
REV
3600 Imp/KWh
"LED Von glowing"
Voltage Phase present
kWh
x1000
V
ON
I
REV
3600 Imp/KWh
"LED Von off"
Voltage phase absent
Setup Parameter Screen
SEL
(Select)
SEL
SEL
SYS
SEriAL
A
(
(
)
Select System
Serial Communication
Parameter
Parameter)
(Sec 4.2.1)
(Sec 4.2.2)
UP
Add
(
)
PT Primary
(Modbus Address)
(Sec 4.2.2.1)
(Sec 4.2.1.1)
US
(
)
PT Secondary
br
(Sec 4.2.1.2)
(Baud Rate)
(Sec 4.2.2.2)
AP
(CT Primary)
Pr
(Sec 4.2.1.3)
(Parity Bits)
(Sec 4.2.2.3)
A
x1000
kWh
V
I
ON
REV
3600 Imp/KWh
"LED IREV glowing"
Current out of phase w.r.t voltage .
x1000
kWh
V
I
ON
REV
3600 Imp/KWh
"LED IREV off"
Current in phase w.r.t voltage
cd
(PassWord)
Exit
from setup Parameter to Main Display
SEL
SEL
rELAY
rESEt
(
Reset
Parameter)
(Select Relay Parameter)
(Sec 4.2.3)
(Sec 4.2.4)
(
non
No Parameter),
dur
( Relay Pulse Duration)
(Sec 4.2.4.1)
E
(Energy),
"Down" key
(Sec 4.2.3.1)
rAt
(Pulse Rate Divisor)
(Sec 4.2.4.2)
: UP KEY
: DOWN KEY
2
quit
A
(Exit Menu)
(Sec 4.2.5)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EM 3490 SS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Rish EM 3490 SS

  • Page 1: Table Of Contents

    EM 3490 SS 3. Phase Indications Single Phase Energy Meter Installation & Operating Instructions Section Contents x1000 x1000 TABLE 1: Introduction Measurement Reading Screen Measured Parameters Units of measurement Phase Indications Display Parameter 3600 Imp/KWh 3600 Imp/KWh Programming Active Energy (8 digit counter) 4.1 Password Protection...
  • Page 2: Programming

    4.2 Menu selection. 4. Programming Password Incorrect. 4.2.1 System Parameter selection screen. The following sections comprise step by step procedures for configuring the 4.2.1 System parameters Selection meter for individual user requirements. The unit has not accepted the Password entered. x1000 To access the set-up screens press and hold the “...
  • Page 3: Address Setting

    Pulse output is the potential free, very fast acting relay contact which can be used to drive an external and advances to the “Energy digit Rollover(reset) count”menu mechanical counter for energy measurement. (See section 4.2.1.5). Rish EM 3490 SS has one pulse output. Reset option select, One normally open & one normally closed Relay Contact x1000 Pressing the “...
  • Page 4: Rs 485 (Modbus) Output

    6. RS 485 ( ModBus ) Output : Response: Volt (239.6V) Meter supports MODBUS (RS485) RTU protocol( 2-wire ) . Connection should be made using twisted pair shielded cable. All "A" and "B" connections are daisy chained 01 (Hex) 04 (Hex) 04 (Hex) 43 (Hex) 6E (Hex)
  • Page 5: User Assignable Modbus Register

    Reading Parameter data through User Assignable Registers: Table 10 : User Assignable mapping register ( 4X registers) Explanation for 4 X register : Table 6 : RS 485 Set-up Code Address Parameter Modbus Start Address (Hex) In assigning query Voltage and Power Factor1 parameters were assigned to 0x 200 and Mapping Register (Register) Number.
  • Page 6: Phaser Diagram

    7. Phaser Diagram : 10. Specification : Nominal range of use of influence quantities for measurands 8.1 EMC Installation Requirements System Voltage 50 .. 120 % of Rated Value This product has been designed to meet the certification of the EU directives 1 Phase 2 Wire (Single Phase) when installed to a good code of practice for EMC in industrial environments, Current...
  • Page 7 11. Connection for Optional Pulse Output / RS 485 Notes : 11.1 One Pulse Output & RS485 Pulse out RS 485 NO NC COM 11.2. RS 485 Output RS 485 11.3. One Pulse Output Pulse out NO NC COM The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and is intended to describe the correct method of installation for this product.