Gas Leakage Error(Error Code : E554) - Samsung AC071MN4PKH Service Manual

Hide thumbs Also See for AC071MN4PKH:
Table of Contents

Advertisement

4-4-20. Gas leakage error(Error Code : E554)

1. Test items
1) Check the power connection. / Check the restart after power reset.
Is there a fault in input power? (Single-phase : 220Vac, 3-phase : 380Vac)
Does error occur again at operation after power is reset?
2) Check the compressor and the state of compressor wire assembling.
3) Check the outdoor unit installation environment.
Check for disconnection of the wires regarding the Inverter PCB of the outdoor unit and check the installation environment.
At the site where several units were installed at the same time, check whether communication wire and pipes have been wrongly connected!
2. Check procedure
Power on 30 seconds after power off.
Power on 30 seconds after power off.
Check the
compressor
and its connecting wires.
1. Are all the resistance values between
phases matched? (U
2. Is compressor wiring normal?
(disconnection, wrong connection)
3. Is there any abnormal
noise from compressor
rotation?
Is indoor and outdoor unit wiring/piping
installed properly?
Continue
Yes
V, U
W, V
W)
Yes
Yes
No
1. Replace the compressor : If the resistance value
between phases of the compressor is different.
Power on.
End the service.
2. Reassemble wire : If the wire connection of the
No
compressor is wrong.
Power on.
End the service.
3. Replace the compressor : When loud abnormal
noise generates (metal cutting or grinding noise),
or severe vibration.
No
Install again by following the standard specifications.
Piping
Wiring
4-51
Troubleshooting
End the service.
Check the normal operation.
Check the normal operation.
Bad installation