3.3 Side-by-side mounting

If several controllers are mounted side-by-side or above one another in a control panel,
the horizontal distance between panel cutouts must be a minimum of 11 mm and the
vertical distance a minimum of 50 mm.

3.4 Mounting the controller in a panel cutout

*
Remove the frame
*
Fit the seal supplied with the controller
Attention!
The controller must be installed with the seal, preventing water or dirt from
entering the housing!
(1)
7866z02/0112
Figure 3: Mounting in a panel cutout
*
Insert the controller from the front into the panel cutout (1) and make certain the seal
is correctly fitted
*
Fit the frame from the rear (2) and let it engage in the grooves
*
Tighten the screws evenly with a screwdriver (3) until the controller is correctly
secured in the panel cutout
(3)
(2)
(3)
15/68