Note: The multi-outlet device menu is inaccessible if there are no devices configured
with pmoutlet parameter in /etc/portslave/pslave.conf. You need to configure the
"sxx.pmoutlet" line in pslave.conf file.
In the following example, the Sun Server is a multi-outlet device connected to outlet 7
of IPDU 1 and outlet 2 of IPDU 2. The sequence of power up interval is 1.7 then 2.2.
s3.pmoutlet 1.7, 2.2
s3. alias
To Manage Multiple IPDUs from the Command Line
Step 1 - Connect to the CONSOLE port of the ACS or use Telnet or SSH to
access the ACS, and log in.
Step 2 - Enter the pm command.
[root@CAS root]# pm
The power management menu displays as shown in the following screen example.
Cyclades Corporation
Power Management Menu v1.0
-----------------------------------------------------------
-----------------------------------------------------------
Cyclades Power Management Menu
-----------------------------------------------------------
1. Exit 2. individual ipdus
Please choose an option:
To control power on multi-outlet devices, Enter the number 3. .
1. Exit 2. individual ipdus
Please choose an option: 3
AlterPath ACS Command Reference Guide
Power Management with AlterPath™ PM Integration
Sun Server
3. multi-outlet device
3. multi-outlet device
4.Info
4.Info
231