Siemens SIMATIC ET 200SP HA Manual page 56

Analog input module ai 16xtc/ 8xrtd 2-/3-/4-wire ha
Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Drivers, parameters, diagnostics messages and address space
A.4 Diagnostics messages and maintenance events
Maintenance messages have no direct effect on the function of the module or the analog value
acquisition.
Table A-11
Maintenance messages, their meaning and possible remedies
Maintenance
Error
message
code
Redundancy part‐
120
H
ner has different
hardware/firm‐
ware version
IO redundancy
121
H
warning
Retentive memo‐
154
H
ry in carrier mod‐
ule defective
Retentive memo‐
155
H
ry in the terminal
block defective
56
Assignment
Meaning / Cause
Module
The redundantly configured and intercon‐
nected I/O modules are not compatible
Module
Unable to correctly communicate with the
partner module
Module
Fault detected in the data block on the carri‐
er module during operation
Module
An error in the memory module on the ter‐
minal block was recognized during operation
Analog input module AI 16xTC/8xRTD 2-/3-/4-wire HA (6DL1134-6JH00-0PH1)
Solution
● Check the module and
replace it
● Update the firmware
● Check the redundancy
connection
● Check the redundant
modules
● Check and replace terminal
block if necessary
Replace carrier module
Replace terminal block
Manual, 05/2017, A5E39408175-AA