Siemens SIMATIC ET 200SP HA Manual page 44

Analog input module ai 16xtc/ 8xrtd 2-/3-/4-wire ha
Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Drivers, parameters, diagnostics messages and address space
A.2 Parameter assignment
Error_
Error_
Cause
Code_1
Code_2
0xE1
0x01
Reserved bit set
0xE1
0x03
Invalid hardware interrupt enable bit set for operating mode
0xE1
0x04
Invalid value for hardware interrupt limit
0xE1
0x05
Invalid coding for measuring range / measurement type
0xE1
0x08
Invalid coding for interference frequency suppression / in‐
tegration time
0xE1
0x09
Invalid coding for smoothing
0xE1
0x0E
Invalid redundancy parameter assignment
0xE1
0x0F
Invalid parameter assignment of the reference temperature
(Pt100 climate)
0xE1
0x10
Invalid type of measurement
0xE1
0x11
Invalid measuring range
Valid parameters
Only the values specified in the following are permitted. Values that are not listed are rejected
by the module.
Every parameter data record is checked by the module. If an incorrect parameter is detected,
the entire data record is rejected and the parameters of the module remain unchanged.
44
Analog input module AI 16xTC/8xRTD 2-/3-/4-wire HA (6DL1134-6JH00-0PH1)
Solution
Check and correct the parameters
Manual, 05/2017, A5E39408175-AA