Notifier AFP-300 Manual page 4

Analog fire panels
Hide thumbs Also See for AFP-300:
Table of Contents

Advertisement

The CPU-300/400
EIA-232
Terminal Port
EIA-232
Printer Port
Slide-in Label
EPROM
The MPS-400
Main Power Supply
AC Power 120/240 VAC
(Field Selectable)
Battery (12-60 A.H.)
UZC Coder Input
Door Tamper Switch (STS-200)
Page 4 of 10 — DN-5262 • 10/31/05
EIA-485 Port
"Terminal Mode"
EIA-485 Port
Resettable
2 non-resettable
24 VDC @
24 VDC circuits
1.25 amps*
rated 1.25 amps
each*
Meter Module Option (MPM-2)
SLC Loop #1
(Style 4, 6, or 7)
SLC Loop #2 (AFP-400 only)
(Style 4,6, or 7)
Form-C Alarm, Trouble, Supervisory,
and Security contacts. (3 amps @ 30
VDC) ( Note: Supervisory and Security
contacts can be converted to alarm
contacts.)
*The MPS-400 is a 6 amp
power supply. Total power,
including internal modules,
cannot exceed 6 amps.
80-Character (2 x 40)
Back-Lit LCD Display
Status LED's
Control Switches
Programming
Keypad
Flip-Down Door
(covers the
programming
keypad)
NAC or Releasing
circuits 1 & 2.
Class A or Class B,
24 VDC @ 2.5
amps each.*
NAC or Releasing
Circuits 3 & 4.
Class A or B, 24
VDC @ 2.5 amps
each.*
Status/Trouble
LEDs
Optional
Transmitter module
(4XTM connector).